3.9 O-##
Options/Comms
3.9.1 O-0# General Settings
O-01 Control Site
Option:
Function:
The setting in this parameter overrides
the settings in
parameter O-56 Preset Reference
[0]
*
Digital and
ctrl.word
Use both digital input and control word.
[1]
Digital only
Use digital inputs only.
[2]
Controlword
only
Use control word only.
O-02 Control Word Source
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the source of the control word: 1 of 2
serial interfaces, or 4 installed options. During
initial power-up, the drive automatically sets
this parameter to
[3] Option A
if it detects a
valid network option installed in slot A. If the
option is removed, the drive detects a change
in the configuration, sets
parameter O-02 Control Word Source
back to
default setting
[1] Drive Port
, and the drive
then trips. If an option is installed after initial
power-up, the setting of
parameter O-02 Control Word Source
does not
change but the drive trips and displays:
alarm
67, Option Changed
.
The drive port is the RS485 port running the
protocol as set in O-30 ([0] Drive, [1] Drive
MC, [2] Modbus RTU, [3] Metasys N2, or [4]
FLN.
[0]
None
[1]
*
Drive Port
The drive port is the RS485 port running the
protocol as set in parameter O-30; Drive, Drive
MC, Modbus RTU, Metasys N2, or FLN.
[2]
USB Port
[3]
Option A
[4]
Option B
[30]
External
Can
O-03 Control Word Timeout Time
Range:
Function:
60.0
s
*
[0.5 -
18000 s]
Enter the maximum time expected to pass
between the reception of 2 consecutive
messages. If this time is exceeded, it indicates
that the serial communication has stopped.
The function selected in
parameter O-04 Control Word Timeout Function
is then carried out.
The object list holds information on the
objects that triggers the control timeout:
•
Analog outputs
•
Binary outputs
•
AV0
•
AV1
•
AV2
•
AV4
•
BV1
•
BV2
•
BV3
•
BV4
•
BV5
•
Multistate outputs
O-04 Control Word Timeout Function
Option:
Function:
Select the timeout function. The
timeout function is activated when the
control word fails to be updated within
the time period specified in
parameter O-03 Control Word Timeout
.
[20] N2 Override Release
only
appears after setting the Metasys N2
protocol.
[0]
*
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[20]
N2 Override
Release
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D