F-10 Electronic Overload
Option:
Function:
[0]
No protection
If the motor is continuously overloaded,
and no warning or trip of frequency
converter is wanted.
[1]
Thermistor
warning
Activates a warning when the connected
thermistor in the motor reacts in the event
of motor overtemperature.
[2]
Thermistor trip Stops (trips) the frequency converter when
the connected thermistor in the motor
reacts in the event of motor overtem-
perature.
[3]
Elec. OL
Warning 1
[4]
*
Elec. OL Trip 1
[5]
Elec. OL
Warning 2
[6]
Elec. OL Trip 2
[7]
Elec. OL
Warning 3
[8]
Elec. OL Trip 3
[9]
Elec. OL
Warning 4
[10]
Elec. OL Trip 4
[20]
ATEX ETR
[21]
Advanced ETR
Electronic Overload functions 1-4 calculate the load when
the set-up where they were selected is active. For example
Elec. OL Warning 3 or Trip 3 starts calculating when set-up
3 is selected. For the North American market: The
Electronic Overload functions provide class 20 motor
overload protection in accordance with NEC.
Illustration 3.5 Thermal Motor Protection
NOTICE
If the temperature of the motor is monitored through a
thermistor or a KTY Sensor, the PELV is not complied
with in case of short circuits between motor windings
and the sensor. To comply with PELV, isolate the sensor
appropriately.
NOTICE
The Electronic Overload timer function does not work
when
parameter P-20 Motor Construction
[1] PM, non-
salient SPM
.
NOTICE
For correct operation of the Electronic Overload function,
the setting in
parameter H-43 Torque Characteristics
must
fit the application (see description of
parameter H-43 Torque Characteristics
).
3.2.3.1 PTC Thermistor Connection
Illustration 3.6 PTC Profile
Using a digital input and 10 V as supply:
Example: The frequency converter trips when the motor
temperature is too high.
Parameter set-up:
•
Set
parameter F-10 Electronic Overload
to
[2]
Thermistor Trip
.
•
Set
parameter F-12 Motor Thermistor Input
to
[6]
Digital Input
.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
37
3