LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PHASE DISTANCE APPLIED TO POWER TRANSFORMERS
CHAPTER 15: THEORY OF OPERATION
The results are shown in the following table.
Table 23: Quadrilateral phase A to ground element analysis
All the comparators and the overcurrent supervision are satisfied. The quadrilateral phase
A ground element will operate for this fault.
Other phase and ground distance elements
Repeating the analysis in the preceding sections for each phase and ground distance
element, it follows that only the ground element in phase A will operate for this fault.
Phase distance applied to power transformers
As a wye-delta transformer introduces discontinuity for the zero-sequence circuit, the
ground distance protection cannot be applied, except special circumstances, to respond to
faults behind the transformer.
The phase distance elements, however, could be developed so that both accurate reach
and correct fault phase identification is retained for faults behind the power transformer
as seen from the relaying point. Without appropriate compensation, the D90
Plus
reach
would depend on a type of fault, creating considerable difficulties in applying protection.
The D90
Plus
provides for any location of the VTs and CTs with respect to the involved power
transformer and the direction of any given zone. In the following equations, the VT and CT
locations are referenced as
None
if the transformer is not present between the CT/VT and
the intended reach point. Otherwise, the location is to be selected as a type of a
transformer as seen from the VT/CT position towards the intended reach point. The
following figure explains the adopted rules.
Parameter
Calculation
Requirement
Condition met
Overcurrent supervision
3 × 1.37 A = 4.09 A
> 3 A
Yes
Reactance difference angle
| –3.9° – 24.8° | = 28.7°
< 75°
Yes
Zero-sequence directional
difference angle
| 19.8° – 0.0° | = 19.8°
< 75°
Yes
Negative-sequence directional
difference angle
| 19.8° – 0.0° | = 19.8°
< 75°
Yes
Right blinder difference angle
| –93.0° – (–109.2°) | = 16.2° < 90°
Yes
Left blinder difference angle
| 82.9° – 108.7° | = 25.8°
< 90°
Yes
Fault type comparator
difference angle
| 19.8° – 19.8° | = 0.0°
< 50°
Yes
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...