514
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
TRANSIENT RECORDER
CHAPTER 10: DIGITAL FAULT RECORDER
Front panel indications
The digital fault reporter summary screen provides an indication that the transient
recorder is ready to capture data and has memory available. In protected mode, the
Ready
to Capture
indication is green when all of the following conditions hold.
•
The transient recorder is enabled.
•
The block trigger input is not asserted.
•
Memory is available.
•
A record capture is not currently in progress.
Otherwise the indication is red. In automatic overwrite mode, the
Ready to Capture
indication is green when all of the following conditions hold.
•
The transient recorder is enabled.
•
The block trigger input is not asserted.
•
A record capture is not currently in progress.
The
Memory Available
indication is green when less than 80% of the memory has been
filled. It is yellow when the amount of memory filled is between 80% and 99%, and it is red
if 100% of the memory is filled.
Figure 442: Digital fault reporter summary screen
The transient recorder screen shows the individual records stored on the device. This
screen also has an indication of any active triggers (red indication) for the transient
recorders. If a continuous trigger is permanently active, it will not fill the memory of the
recorder. After the first record is generated it is effectively disabled by the trigger logic;
however, its status will be displayed on this screen. The user can also force triggering of the
recorder from this screen.
Figure 443: Transient recorder screen
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...