CHAPTER 7: PROTECTION
PROTECTION FLEXLOGIC™
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
423
PHASE OV1 DPO B.....................................Asserted when phase B of the phase overvoltage 1 element
drops out.
PHASE OV1 DPO C.....................................Asserted when phase C of the phase overvoltage 1 element
drops out.
PHASE OV1 OP.............................................Asserted when at least one phase of the phase overvoltage 1
element operates.
PHASE OV1 OP A.........................................Asserted when phase A of the phase overvoltage 1 element
operates.
PHASE OV1 OP B.........................................Asserted when phase B of the phase overvoltage 1 element
operates.
PHASE OV1 OP C.........................................Asserted when phase C of the phase overvoltage 1 element
operates.
PHASE OV1 PKP...........................................Asserted when at least one phase of the phase overvoltage 1
element picks up.
PHASE OV1 PKP A ......................................Asserted when phase A of the phase overvoltage 1 element
picks up.
PHASE OV1 PKP B ......................................Asserted when phase B of the phase overvoltage 1 element
picks up.
PHASE OV1 PKP C ......................................Asserted when phase C of the phase overvoltage 1 element
picks up.
PHASE OV2
....................................................Same set of operands as shown above for the phase
overvoltage 2 element.
Phase select operands
PHASE SELECT 3P.......................................Asserted when a three-phase symmetrical fault is detected.
PHASE SELECT AB ......................................Asserted when a phase A to B fault is detected.
PHASE SELECT ABG...................................Asserted when a phase A to B to ground fault is detected.
PHASE SELECT AG......................................Asserted when a phase A to ground fault is detected.
PHASE SELECT BC ......................................Asserted when a phase B to C fault is detected.
PHASE SELECT BCG...................................Asserted when a phase B to C to ground fault is detected.
PHASE SELECT BG......................................Asserted when a phase B to ground fault is detected.
PHASE SELECT CA ......................................Asserted when a phase C to A fault is detected.
PHASE SELECT CAG...................................Asserted when a phase C to A to ground fault is detected.
PHASE SELECT CG......................................Asserted when a phase C to ground fault is detected.
PHASE SELECT MULTI-P...........................Asserted when a multi-phase fault is detected.
PHASE SELECT SLG....................................Asserted when a single line to ground fault is detected.
PHASE SELECT VOID..................................Asserted when the fault type cannot be detected.
Phase time overcurrent operands
PHASE TOC1 DPO.......................................Asserted when at least one phase of the phase time
overcurrent 1 element drops out.
PHASE TOC1 DPO A...................................Asserted when phase A of the phase time overcurrent 1
element drops out.
PHASE TOC1 DPO B...................................Asserted when phase B of the phase time overcurrent 1
element drops out.
PHASE TOC1 DPO C...................................Asserted when phase C of the phase time overcurrent 1
element drops out.
PHASE TOC1 OP..........................................Asserted when at least one phase of the phase time
overcurrent 1 element operates.
PHASE TOC1 OP A......................................Asserted when phase A of the phase time overcurrent 1
element operates.
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...