SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
Protection specifications
AUTORECLOSURE
Applications: .........................................................two breakers
Tripping schemes: ..............................................single-pole and three-pole
Reclose attempts:...............................................up to 4 before lockout
Reclosing mode:..................................................selectable
Breaker sequence: .............................................selectable
AUXILIARY OVERVOLTAGE
Pickup level:...........................................................0.000 to 1.100 pu in steps of 0.001
Dropout level: .......................................................<98% of pickup
Level accuracy:....................................................±0.5% of reading from 10 to 208 V
Pickup delay:.........................................................0.00 to 600.00 seconds in steps of 0.01
Reset delay: ...........................................................0.00 to 600.00 seconds in steps of 0.01
Timing accuracy: ................................................±3% of operate time or ±4 ms (whichever is greater)
Operate time:........................................................<2 cycles at 1.10 × pickup at 60 Hz
AUXILIARY UNDERVOLTAGE
Pickup level:...........................................................0.000 to 1.100 pu in steps of 0.001
Dropout level: .......................................................>102% of pickup
Level accuracy:....................................................±0.5% of reading from 10 to 208 V
Curve shapes:.......................................................GE IAV inverse, definite time
Curve multiplier:..................................................0.00 to 600.00 in steps of 0.01
Timing accuracy: ................................................±3% of operate time or ±4 ms (whichever is greater)
BREAKER FAILURE
Mode:........................................................................single-pole, three-pole
Current supervision: ..........................................phase current, neutral current
Supervision pickup:............................................0.001 to 30.000 pu in steps of 0.001
Supervision dropout:.........................................<98% of pickup
Supervision accuracy at 0.1 to 2.0 × CT:..±2% of rated
Supervision accuracy at >2.0 × CT:............±2.5% of reading
Time accuracy: ....................................................±3% or 4 ms (whichever is greater)
BREAKER FLASHOVER
Operating quantity: ...........................................phase current, voltage, and voltage difference
Pickup level voltage:..........................................0.000 to 1.500 pu in steps of 0.001
Dropout level voltage: ......................................97 to 98% of pickup
Pickup level current: ..........................................0.000 to 1.500 pu in steps of 0.001
Dropout level current:.......................................97 to 98% of pickup
Level accuracy:....................................................±0.5% or ±0.1% of rated (whichever is greater)
Pickup delay:.........................................................0.000 to 65.535 seconds in steps of 0.001
Time accuracy: ....................................................±3% or ±42 ms (whichever is greater)
Operate time:........................................................<42 ms at 1.10 × pickup at 60 Hz
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...