611
Remote Command Password
Range: up to 12 visible ASCII characters (see restrictions above)
Default: null
The value of the remote command password is specified here. For the password to be
successfully entered, the values in the
Enter New Password
and
Confirm New Password
fields must be identical.
If an entered password is lost (or forgotten), consult the factory with the corresponding
Encrypted Password
value.
Remote Setting Password
Range: up to 12 visible ASCII characters (see restrictions above)
Default: null
The value of the remote setting password is specified here. For the password to be
successfully entered, the values in the
Enter New Password
and
Confirm New Password
fields must be identical.
If an entered password is lost (or forgotten), consult the factory with the corresponding
Encrypted Password
value.
The access supervision settings allow the user to specify the length of inactivity required
before returning to the restricted access level. The following access supervision settings
are available.
Command Password Access Timeout
Range: 5 to 480 minutes in steps of 1
Default: 5 minutes
This setting specifies the length of inactivity (no local or remote access) required to
return to restricted access from the command password level.
Setting Password Access Timeout
Range: 5 to 480 minutes in steps of 1
Default: 30 minutes
This setting specifies the length of inactivity (no local or remote access) required to
return to restricted access from the setting password level.
Invalid Password Attempts
Range: 2 to 5 in steps of 1
Default: 3
This setting specifies the number of times an incorrect password can be entered within a
three-minute time span before lockout occurs and applies to both the setting and
command passwords.
When lockout occurs for the command password level, the
ACCESS LOC CMND DENY
and
ACCESS REM CMND DENY
communication operands are set to “On”. These operands are
returned to the “Off” state upon expiration of the lockout. Likewise, when lockout occurs
for the setting password level, the
ACCESS LOC SETG DENY
and
ACCESS REM SETG DENY
communication operands are set to “On”. These operands are also returned to the “Off”
state upon expiration of the lockout.
Password Lockout Duration
Range: 5 to 60 minutes in steps of 1
Default: 5 minutes
This setting specifies the time that the D90
Plus
will lockout command password access
after the number of invalid password entries specified by the
Invalid Password Attempts
setting has occurred.
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...