DEVICE OVERVIEW
CHAPTER 2: PRODUCT DESCRIPTION
For additional information, refer to:
Application to series-compensated lines
The D90
Plus
provides enhanced stability and security by employing an adaptive distance
reach control to cope with the overreaching and sub-synchronous oscillations when
applied to, or in the vicinity of, series compensated lines. For directional integrity the relay
uses memory voltage polarization and a multi-input comparator is used to deal with
current inversion issues in series compensated lines.
For additional information, refer to:
Series compensated line protection application guidelines
In-zone transformer compensation
Phase distance elements in the D90
Plus
can be used to detect faults through different types
of three-phase wye or delta transformers, allowing application of the D90
Plus
for backup
protection on generators. VTs and CTs can be installed independently of each other on
either side of the power transformer. The relay automatically compensates for transformer
connections, to guarantee accurate reach for any type of fault.
For additional information, refer to:
Phase distance applied to power transformers
Load encroachment
The reliable load encroachment feature offers excellent discrimination between keep
loading conditions and fault conditions especially for long lines under heavy loads by
supervising the distance elements or any overcurrent element. This prevents unwarranted
tripping under heavy line load conditions and enables optimum operation of the line while
meeting regulatory requirements for the loading.
The following diagram illustrates distance quadrilateral characteristics supervised by load
encroachment function.
Figure 9: Load encroachment characteristic example
For additional information, refer to:
Fault locator
The integrated fault locator provides distance to fault in kilometers or miles.
$&'5
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...