DEVICE OVERVIEW
CHAPTER 2: PRODUCT DESCRIPTION
Overfrequency and underfrequency protection
The multiple stages of underfrequency and over frequency elements can be used to
initiate load shedding or remedial actions schemes or frequency-based load restoration
schemes during lack of generation in the network or due to sudden load drops. When
combined with the advanced automation capabilities of the D90
Plus
, flexible special
protection schemes can be built.
For additional information, refer to:
Overcurrent functions
The D90
Plus
provides overcurrent functions for phase, neutral, and ground which can run
parallel with distance protection or can be programmed to provide primary protection
under conditions when distance elements are blocked during fuse-failure conditions.
•
Instantaneous and timed overcurrent elements for phase, neutral, ground, and
negative-sequence protection.
•
Directional supervision is available for phase, neutral, and negative-sequence
elements.
•
Time overcurrent elements can individually be set to use IEEE, IEC, or custom
FlexCurves™.
For additional information, refer to:
Autoreclose
The D90
Plus
provides multi-shot autoreclosing for single-pole or three-pole autoreclose on
all types of faults with independently programmable dead times for each shot.
Autoreclosing also can be dynamically blocked by user programmable logic. Four different
autoreclose modes are available enabling the users to select the reclosing mode of their
practice.
For additional information, refer to:
Breaker failure
The D90
Plus
can be used to carry out fully independent breaker failure protection over the
breakers associated to the line when connected to a substation with a breaker-and-a-half
or ring bus arrangement. The D90
Plus
provides the required current source inputs, digital
inputs and outputs, and elements to perform two independent breaker failure functions.
For additional information, refer to:
Multi-breaker configurations
The D90
Plus
supports multi-breaker busbar configurations such as breaker-and-a-half or
ring bus arrangements, providing dual breaker autoreclose, dual synchrocheck elements,
and dual independent breaker failure elements.
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...