CHAPTER 6: COMMUNICATIONS
USER-PROGRAMMABLE SELF-TESTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
143
Figure 117: User-programmable self-test configuration settings
The following settings are available to configure the user-programmable self-tests.
Ethernet Port 1 Fail Function
Range: Enabled, Disabled
Default: Enabled
When this setting is “Disabled”, the ETHERNET PORT 1 FAILURE alarm will not assert a
FlexLogic™ operand or write to the event recorder. Moreover, it will not trigger the ANY
MINOR ALARM or ANY SELF-TEST messages. When this setting is “Enabled”, the
ETHERNET PORT 1 FAILURE alarm continues to function along with other major and
minor alarms. Refer to the
Relay self-tests
section in for additional information on major
and minor self-test alarms.
Ethernet Port 2 Fail Function
Range: Enabled, Disabled
Default: Disabled
When this setting is “Disabled”, the ETHERNET PORT 2 FAILURE alarm will not assert a
FlexLogic™ operand or write to the event recorder. Moreover, it will not trigger the ANY
MINOR ALARM or ANY SELF-TEST messages. When this setting is “Enabled”, the
ETHERNET PORT 2 FAILURE alarm continues to function along with other major and
minor alarms. Refer to the
Relay self-tests
section in for additional information on major
and minor self-test alarms.
Ethernet Port 3 Fail Function
Range: Enabled, Disabled
Default: Disabled
When this setting is “Disabled”, the ETHERNET PORT 3 FAILURE alarm will not assert a
FlexLogic™ operand or write to the event recorder. Moreover, it will not trigger the ANY
MINOR ALARM or ANY SELF-TEST messages. When this setting is “Enabled”, the
ETHERNET PORT 3 FAILURE alarm continues to function along with other major and
minor alarms. Refer to the
Relay self-tests
section in for additional information on major
and minor self-test alarms.
SNTP Fail Function
Range: Enabled, Disabled
Default: Enabled
When this setting is “Disabled”, the SNTP FAILURE alarm will not assert a FlexLogic™
operand or write to the event recorder. Moreover, it will not trigger the ANY MINOR
ALARM or ANY SELF-TEST messages. When this setting is “Enabled”, the SNTP FAILURE
alarm continues to function along with other major and minor alarms. Refer to the
Relay
self-tests
section in for additional information on major and minor self-test alarms.
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...