488
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
AUTOMATION LOGIC
CHAPTER 8: AUTOMATION
Aut VO 2
to
255
...........................................The operands listed above are available for the automation
virtual outputs 2 through 255. These operands will reflect the
programmed names for the automation virtual outputs.
Breaker control operands
BKR CNTRL1 CLOSE CMD .......................Asserted when a close command is issued on breaker 1 from
breaker control.
BKR CNTRL1 INTERLCK BYPS................Asserted when interlocking is bypassed for breaker 1.
BKR CNTRL1 OPEN CMD.........................Asserted when an open command is issued on breaker 1 from
breaker control.
BKR CNTRL2
.................................................The operands listed above are also available for all breakers.
Breaker interlocking operands
BKR INTERLK1 CLS PERM........................Asserted when all conditions have been satisfied for closing
breaker 1.
BKR INTERLK1 OPEN PERM....................Asserted when all conditions have been satisfied for opening
breaker 1.
BKR INTERLK1 TAGGED ...........................Asserted when a tag is applied to breaker 1.
BKR INTERLK2
..............................................The operands listed above are available all breaker interlocking
elements.
Automation contact input operands
Cont Ip 1 OFF...............................................Asserted when the field contact connected to contact input 1 is
opened.
Cont Ip 1 ON.................................................Asserted when the field contact connected to contact input 1 is
closed.
Cont Ip 1 TRB OFF......................................Asserted when there are no problems with contact input 1.
Cont Ip 1 TRB ON........................................Asserted when there is an internal or external problem with
contact input 1.
Cont Ip 2
to
40
.............................................The operands listed above are available for automation
contact inputs 2 through 40. These operands will reflect the
programmed names for the automation contact inputs.
Automation contact output operands
Cont Op 1 IOff..............................................Asserted when contact output 1 with current monitoring is
opened.
Cont Op 1 IOn..............................................Asserted when contact output 1 with current monitoring is
closed.
Cont Op 1 VOff............................................Asserted when contact output 1 with voltage monitoring is
opened.
Cont Op 1 VOn.............................................Asserted when contact output 1 with voltage monitoring is
closed.
Cont Op 2
to
40
...........................................The operands listed above are available for automation
contract outputs 2 through 40. These operands will reflect the
programmed names for the automation contact outputs.
Disconnect control operands
DISC CNTRL1 CLOSE CMD......................Asserted when disconnect 1 is closed.
DISC CNTRL1 INTERLCK BYPS...............Asserted when interlocking has been bypassed for disconnect
1.
DISC CNTRL1 LOCAL SELECT ................Asserted when disconnect 1 has been selected from the front
panel HMI.
DISC CNTRL1 OPEN CMD........................Asserted when disconnect 1 is open.
DISC CNTRL1 REMOTE SELECT.............Asserted when disconnect 1 has been selected from SCADA.
DISC CNTRL2
................................................The operands listed above are available all disconnects.
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...