CHAPTER 11: METERING
PHASOR MEASUREMENT UNIT
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
545
Figure 473: Power triggering configuration settings
The following settings are available for each phasor measurement unit.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the phasor measurement unit power triggering
function.
Active
Range: 0.250 to 3.000 pu in steps of 0.001
Default: 1.250 pu
This setting specifies the pickup threshold for the active power of the source. For single-
phase power, 1 pu represents the product of 1 pu voltage and 1 pu current, or the
product of nominal secondary voltage, the VT ratio, and the nominal primary current.
For the three-phase power, 1 pu is three times the value for single-phase power. The
comparator applies a 3% hysteresis.
Reactive
Range: 0.250 to 3.000 pu in steps of 0.001
Default: 1.250 pu
This setting specifies the pickup threshold for the reactive power of the source. For
single-phase power, 1 pu represents the product of 1 pu voltage and 1 pu current, or the
product of nominal secondary voltage, the VT ratio and the nominal primary current. For
the three-phase power, 1 pu is three times the value for single-phase power. The
comparator applies a 3% hysteresis.
Apparent
Range: 0.250 to 3.000 pu in steps of 0.001
Default: 1.250 pu
This setting specifies the pickup threshold for the apparent power of the source. For
single-phase power, 1 pu represents the product of 1 pu voltage and 1 pu current, or the
product of nominal secondary voltage, the VT ratio and the nominal primary current. For
the three-phase power, 1 pu is three times the value for single-phase power. The
comparator applies a 3% hysteresis.
Pickup Time
Range: 0.00 to 600.00 seconds in steps of 0.01
Default: 0.10 seconds
This setting may be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...