CHAPTER 11: METERING
PHASOR MEASUREMENT UNIT
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
553
PDC Control
Range: Enabled, Disabled
Default: Disabled
The synchrophasor standard allows for user-defined controls originating at the PDC, to
be executed on the phasor measurement unit. The control is accomplished via an
extended command frame. The relay decodes the first word of the extended field,
EXTFRAME, to drive 16 dedicated FlexLogic™ operands:
PDC NETWORK CNTRL 1
(from the
least significant bit) to
PDC NETWORK CNTRL 16
(from the most significant bit). Other words,
if any, in the EXTFRAME are ignored. The operands are asserted for 5 seconds following
reception of the command frame. If the new command frame arrives within the 5
second period, the FlexLogic™ operands are updated, and the 5 second timer is re-
started.
This setting enables or disables the control. When enabled, all 16 operands are active;
when disabled, all 16 operands remain reset.
TCP Port Number
Range: 1 to 65535 in steps of 1
Default: 4712
This setting selects the TCP port number that will be used for network reporting.
UDP Port Number
Range: 1 to 65535 in steps of 1
Default: 4713
This setting selects the UDP port number that will be used for network reporting.
Phasor measurement unit one-shot
The phasor measurement unit one-shot feature allows pre-scheduling a phasor
measurement unit measurement at a specific point in time. This functionality can be used
to test for accuracy of the phasor measurement unit, and for manual collection of
synchronized measurements through the system.
Phasor measurement unit one-shot settings
Select the
Settings > Metering > Phasor Measurement Unit > One-Shot
menu item to
open the phasor measurement unit one-shot window.
Figure 482: Phasor measurement unit one-shot configuration settings
The following settings are available for each phasor measurement unit.
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...