CHAPTER 6: COMMUNICATIONS
NETWORK SETTINGS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
91
The single IP redundancy configuration provides compatibility with UR-series relays and
other devices with single-IP redundancy, and provides a maximum level of switchover
performance. In this configuration, the port 2 IP address, subnet mask, and gateway
address are used and the port 3 settings are ignored. All communications traffic will
normally be routed on port 2. If a failure occurs (determined at the hardware layer upon
detecting loss of link signal on the active channel) then the traffic is re-routed to port 3.
Switchover to port 3 takes place in less than 10 ms from the moment that the physical
layer detects a failure. The device reverts from port 3 to port 2 as soon as port 2 becomes
available, regardless of the state of port 3. Switchover to port 2 takes place in less than
500 ms. A link pulse is maintained in the transmit direction on both ports regardless of
which port is in use. This ensures that communications are established with minimal
delays. An Ethernet broadcast message is transmitted immediately upon switching ports,
thereby forcing all Ethernet switches in the network to immediately update their routing
tables.
In the dual IP redundancy configuration, each port has a unique IP address, subnet mask,
and gateway address. Multiple client-server connections may be opened on each port
simultaneously. Under normal conditions, GOOSE messages are sent on both ports.
Select the
Settings > Communications > Network > Ethernet
menu item to open the
Ethernet configuration window. A selection of settings, commands, and actual values is
available.
Figure 73: Ethernet port configuration settings
Содержание D90 Plus
Страница 10: ...x D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 438: ...428 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PROTECTION FLEXANALOG PARAMETERS CHAPTER 7 PROTECTION ...
Страница 502: ...492 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL AUTOMATION FLEXANALOG PARAMETERS CHAPTER 8 AUTOMATION ...
Страница 626: ...616 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ENERVISTA SECURITY MANAGEMENT SYSTEM CHAPTER 13 SECURITY ...
Страница 678: ...668 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SINGLE POLE TRIPPING CHAPTER 15 THEORY OF OPERATION ...
Страница 684: ...674 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 16 MAINTENANCE ...
Страница 686: ...676 D90PLUS LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER 17 APPENDIX ...