5-90
C70 Capacitor Bank Protection and Control System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Select the
DIRECT I/O DATA RATE
to match the data capabilities of the communications channel. All IEDs communicating
over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel communica-
tions cards apply the same data rate to both channels. Delivery time for direct input and output messages is approximately
0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’.
The G.703 modules are fixed at 64 kbps. The
DIRECT I/O DATA RATE
setting is not applicable to these modules.
Table 5–12: DIRECT INPUT AND OUTPUT DATA RATES
MODULE
CHANNEL
SUPPORTED DATA RATES
74
Channel 1
64 kbps
Channel 2
64 kbps
7L
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7M
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7P
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7T
Channel 1
64 kbps, 128 kbps
7W
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7V
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
2A
Channel 1
64 kbps
2B
Channel 1
64 kbps
Channel 2
64 kbps
2G
Channel 1
128 kbps
2H
Channel 1
128 kbps
2I
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
2J
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
76
Channel 1
64 kbps
77
Channel 1
64 kbps
Channel 2
64 kbps
75
Channel 1
64 kbps
Channel 2
64 kbps
7E
Channel 1
64 kbps
Channel 2
64 kbps
7F
Channel 1
64 kbps
Channel 2
64 kbps
7G
Channel 1
64 kbps
Channel 2
64 kbps
7Q
Channel 1
64 kbps
Channel 2
64 kbps
7R
Channel 1
64 kbps
7S
Channel 1
64 kbps
Channel 2
64 kbps
NOTE
Содержание C70
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 452: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 1 OVERVIEW 8 THEORY OF OPERATION 8 ...
Страница 474: ...9 22 C70 Capacitor Bank Protection and Control System GE Multilin 9 4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 486: ...10 12 C70 Capacitor Bank Protection and Control System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 630: ...B 110 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 688: ...F 12 C70 Capacitor Bank Protection and Control System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...