GE Multilin
C70 Capacitor Bank Protection and Control System
5-77
5 SETTINGS
5.2 PRODUCT SETUP
5
See the figure in the
Setting Groups
section in the
Control Elements
section later in this chapter for an example of group
activation.
5.2.11 USER-PROGRAMMABLE SELF TESTS
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most
of the minor alarms can be disabled if desired.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the
ANY MINOR ALARM
or
ANY SELF-TEST
messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the
Relay Self-tests
section in chapter 7 for
information on major and minor self-test alarms.
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
REMOTE DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
FIRST ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
PTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SFP MODULE FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
Содержание C70
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 452: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 1 OVERVIEW 8 THEORY OF OPERATION 8 ...
Страница 474: ...9 22 C70 Capacitor Bank Protection and Control System GE Multilin 9 4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 486: ...10 12 C70 Capacitor Bank Protection and Control System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 630: ...B 110 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 688: ...F 12 C70 Capacitor Bank Protection and Control System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...