5-48
C70 Capacitor Bank Protection and Control System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
RECEPTION
CONFIGURABLE GOOSE
CONFIGURABLE GOOSE 1(16)
CONFIG GSE 1(32) DATA ITEMS
The configurable GOOSE settings allow the C70 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to sixteen different configurable datasets can be configured for reception. This is useful for
intercommunication between C70 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between C70 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a C70 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and
“GGIO3.ST.Ind2.stVal”. The C70 will then create a dataset containing these two data items. The Boolean status values from
these data items can be utilized as remote input FlexLogic operands. First, the
REMOTE DEVICE 1(16) DATASET
setting must
be set to contain dataset “GOOSEIn 1” (that is, the first configurable dataset). Then
REMOTE IN 1(16) ITEM
settings must be
set to “Dataset Item 1” and “Dataset Item 2”. These remote input FlexLogic operands will then change state in accordance
with the status values of the data items in the configured dataset.
Double-point status values may be included in the GOOSE dataset. Received values are populated in the
GGIO3.ST.IndPos1.stVal and higher items.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.MX.AnIn1 and higher items.
Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up).
GGIO3.MX.AnIn1 to GGIO3.MX.AnIn32 can only be used once for all sixteen reception datasets.
CONFIG GSE 1
DATASET ITEMS
ITEM 1:
GGIO3.ST.Ind1.stVal
Range: all valid MMS data item references for
transmitted data
MESSAGE
ITEM 2:
GGIO3.ST.IndPos1.stV
Range: all valid MMS data item references for
transmitted data
MESSAGE
ITEM 3:
None
Range: all valid MMS data item references for
transmitted data
↓
MESSAGE
ITEM 32:
None
Range: all valid MMS data item references for
transmitted data
NOTE
Содержание C70
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 452: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 1 OVERVIEW 8 THEORY OF OPERATION 8 ...
Страница 474: ...9 22 C70 Capacitor Bank Protection and Control System GE Multilin 9 4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 486: ...10 12 C70 Capacitor Bank Protection and Control System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 630: ...B 110 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 688: ...F 12 C70 Capacitor Bank Protection and Control System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...