GE Multilin
C70 Capacitor Bank Protection and Control System
5-129
5 SETTINGS
5.5 FLEXLOGIC
5
Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs and outputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the
default name or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names
are shown in the FlexLogic operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic are listed in the Flex-
Logic operators table.
SELF-
DIAGNOSTICS
(See
Relay Self-
tests
descriptions in
Chapter 7:
Commands and
Targets)
ANY MAJOR ERROR
ANY MINOR ERROR
ANY SELF-TESTS
BATTERY FAIL
CLOCK UNSYNCHRONIZED
DIRECT DEVICE OFF
DIRECT RING BREAK
EQUIPMENT MISMATCH
FLEXLOGIC ERR TOKEN
IRIG-B FAILURE
LATCHING OUT ERROR
MAINTENANCE ALERT
FIRST ETHERNET FAIL
PROCESS BUS FAILURE
PTP FAILURE
REMOTE DEVICE OFF
RRTD COMM FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
SNTP FAILURE
SYSTEM EXCEPTION
TEMP MONITOR
UNIT NOT PROGRAMMED
Any of the major self-test errors generated (major error)
Any of the minor self-test errors generated (minor error)
Any self-test errors generated (generic, any error)
The battery is not functioning. Return power supply module to manufacturer.
Relay is not synchronized to the international time standard
A direct device is configured but not connected
The Direct I/O settings is for a connection that is not in a ring
The configuration of modules does not match the stored order code
A FlexLogic equation is incorrect
"Bad IRIG-B Signal" self-test. See Chapter 7: Commands and Targets.
A difference is detected between the desired and actual latch contact state
A subset of the minor self-test errors generated, see Chapter 7
Link failure detected. See description in
Chapter 7: Commands and targets.
See description in
Chapter 7: Commands and targets
"Bad PTP Signal" self-test as described in Chapter 7
One or more GOOSE devices are not responding
See description in
Chapter 7: Commands and targets
See description in
Chapter 7: Commands and targets
See description in
Chapter 7: Commands and targets
SNTP server is not responding
See description in
Chapter 7: Commands and targets
Monitors ambient temperature and maximum operating temperature
The
Settings > Product Setup > Installation > Relay Settings
setting is
not programmed
TEMPERATURE
MONITOR
TEMP MONITOR
Asserted while the ambient temperature is greater than the maximum
operating temperature (80°C)
USER-
PROGRAMMABLE
PUSHBUTTONS
PUSHBUTTON 1 ON
PUSHBUTTON 1 OFF
ANY PB ON
Pushbutton number 1 is in the “On” position
Pushbutton number 1 is in the “Off” position
Any of twelve pushbuttons is in the “On” position
PUSHBUTTON 2 to 12
Same set of operands as PUSHBUTTON 1
Table 5–16: FLEXLOGIC GATE CHARACTERISTICS
GATES
NUMBER OF INPUTS
OUTPUT IS ‘1’ (= ON) IF...
NOT
1
input is ‘0’
OR
2 to 16
any input is ‘1’
AND
2 to 16
all inputs are ‘1’
NOR
2 to 16
all inputs are ‘0’
NAND
2 to 16
any input is ‘0’
XOR
2
only one input is ‘1’
Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 10 of 10)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Содержание C70
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 452: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 1 OVERVIEW 8 THEORY OF OPERATION 8 ...
Страница 474: ...9 22 C70 Capacitor Bank Protection and Control System GE Multilin 9 4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 486: ...10 12 C70 Capacitor Bank Protection and Control System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 630: ...B 110 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 688: ...F 12 C70 Capacitor Bank Protection and Control System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...