GE Multilin
C70 Capacitor Bank Protection and Control System
5-163
5 SETTINGS
5.6 GROUPED ELEMENTS
5
f) PHASE CURRENT UNBALANCE
(ANSI 60P, IEC PVCB/PTOC)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE CURRENT
PHASE CURRENT UNBALANCE 1(3)
PHASE CURRENT
UNBALANCE 1
CUR UNBALCE 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
CUR UNBALCE 1 DIF
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
CUR UNBALCE 1 BANK
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
CUR UNBALCE 1 INHNT
FACTOR A: 0.0000
Range: –0.1000 to 0.1000 in steps of 0.0001
MESSAGE
CUR UNBALCE 1 INHNT
FACTOR B: 0.0000
Range: –0.1000 to 0.1000 in steps of 0.0001
MESSAGE
CUR UNBALCE 1 INHNT
FACTOR C: 0.0000
Range: –0.1000 to 0.1000 in steps of 0.0001
MESSAGE
CUR UNBALCE 1 STG 1A
PICKUP: 0.020 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 2A
PICKUP: 0.030 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 3A
PICKUP: 0.040 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 4A
PICKUP: 0.050 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 1B
PICKUP: 0.020 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 2B
PICKUP: 0.030 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 3B
PICKUP: 0.040 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 4B
PICKUP: 0.050 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 1C
PICKUP: 0.020 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 2C
PICKUP: 0.030 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 3C
PICKUP: 0.040 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 4C
PICKUP: 0.050 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 1
PKP DELAY: 30.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
CUR UNBALCE 1 STG 2
PKP DELAY: 10.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
CUR UNBALCE 1 STG 3
PKP DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
Содержание C70
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 452: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 1 OVERVIEW 8 THEORY OF OPERATION 8 ...
Страница 474: ...9 22 C70 Capacitor Bank Protection and Control System GE Multilin 9 4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 486: ...10 12 C70 Capacitor Bank Protection and Control System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 630: ...B 110 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 688: ...F 12 C70 Capacitor Bank Protection and Control System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...