5-58
C70 Capacitor Bank Protection and Control System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-104 PROTOCOL
IEC NETWORK CLIENT
ADDRESSES
The C70 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the C70 can connect.
A maximum of two simultaneous connections are supported at any given time.
p) IEC 60870-5-103 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-103
The C70 is provided with optional IEC 60870-5-103 communications capability. This feature is specified as
a software option at the time of ordering. See the
Order Codes
section in chapter 2 for details.
The IEC 60870-5-103 protocol is enabled when the
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
PROTOCOL
set-
ting is set to IEC 60870-5-103.
IEC103 COMMON ADDRESS OF ASDU
: This setting uniquely defines this C70 on the serial line. Select an ID between 0 and
254. This ID does not need to be in sequential order for all stations that communicate with a controller, but it is recom-
mended. Note that RS485 only allows a maximum of 32 slave stations on a communication line, so the entire range of 254
addresses is never exhausted.
IEC103 SYNC TIMEOUT
: This setting defines the time that the C70 waits for a synchronization message. The C70 synchro-
nizes its clock using all available sources, with the source synching more frequently overwriting the time of the other
sources. Since the synchronization message received from the IEC 60870-5-103 master is less frequent than IRIG-B, PTP,
or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs and
none of IRIG-B, PTP, or SNTP is active, the C70 sets the invalid bit in the time stamp of a time-tagged message.
IEC NETWORK
CLIENT ADDRESSES
CLIENT ADDRESS 1:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
CLIENT ADDRESS 2:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
CLIENT ADDRESS 3:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
CLIENT ADDRESS 4:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
CLIENT ADDRESS 5:
0.0.0.0
Range: Standard IPV4 address format
IEC103
PROTOCOL
IEC103 COMMON
ADDRESS OF ASDU: 0
Range: 0 to 254 in steps of 1
MESSAGE
IEC103 SYNC TIMEOUT:
1
Range: 1 to 1440 min in steps of 1
MESSAGE
IEC103 INPUTS
BINARY
Range: see sub-menu below
MESSAGE
IEC103 INPUTS
MEASURANDS
Range: see sub-menu below
MESSAGE
IEC103 COMMANDS
Range: see sub-menu below
Содержание C70
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 452: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 1 OVERVIEW 8 THEORY OF OPERATION 8 ...
Страница 474: ...9 22 C70 Capacitor Bank Protection and Control System GE Multilin 9 4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 486: ...10 12 C70 Capacitor Bank Protection and Control System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 630: ...B 110 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 688: ...F 12 C70 Capacitor Bank Protection and Control System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...