B.4 MEMORY MAPPING
B
3769
RTC Offset
0 to 999999999
ns
1
F004
0
376B
PTP - IRIG-B Delta
-500000000 to 500000000
ns
1
F004
0
Real Time Clock Synchronizing FlexAnalogs (Read Only)
376D
PTP - IRIG-B Delta FlexAnalog
-262143 to 262143
---
1
F004
0
Capacitor Control Actual Values (Read Only) (4 modules)
3780
Capacitor Control 1 Discharge Time
0 to 3600
s
1
F001
0
3781
Capacitor Control 2 Discharge Time
0 to 3600
s
1
F001
0
3782
Capacitor Control 3 Discharge Time
0 to 3600
s
1
F001
0
3783
Capacitor Control 4 Discharge Time
0 to 3600
s
1
F001
0
Field Units (Read/Write Setting) (8 modules)
3800
Field Unit 1 ID
0 to 1
---
1
F205
"U1"
3806
Field Unit 1 Function
0 to 1
---
1
F102
0 (Disabled)
3807
Field Unit 1 Type
0 to 3
---
1
F243
0 (CC-05)
3808
Field Unit 1 Serial Number
1 to1
---
1
F205
"000000000000"
380E
Field Unit 1 Port
1 to 4
---
1
F001
1
380F
...Repeated for Field Unit 2
381E
...Repeated for Filed Unit 3
382D
...Repeated for Filed Unit 4
383C
...Repeated for Filed Unit 5
384B
...Repeated for Filed Unit 6
385A
...Repeated for Filed Unit 7
3869
...Repeated for Filed Unit 8
Field Unit Process Card Ports (Read/Write Setting)
3878
Field Unit 1 Process Card Port
0 to 7
---
1
F244
6 (H1a)
3879
Field Unit 2 Process Card Port
0 to 7
---
1
F244
4 (H2a)
387A
Field Unit3 Process Card Port
0 to 7
---
1
F244
2 (H3a)
387B
Field Unit 4 Process Card Port
0 to 7
---
1
F244
0 (H4a)
387C
Field Unit 5 Process Card Port
0 to 7
---
1
F244
7 (H1b)
387D
Field Unit 6 Process Card Port
0 to 7
---
1
F244
5 (H2b)
387E
Field Unit 7 Process Card Port
0 to 7
---
1
F244
3 (H3b)
387F
Field Unit 8 Process Card Port
0 to 7
---
1
F244
1 (H4b)
Field Unit CT VT Settings (Read/Write Setting) (6 modules)
3890
Remote Phase CT x Origin 1
0 to 16
---
1
F247
0 (None)
3891
Remote Phase CT x Origin 2
0 to 16
---
1
F247
0 (None)
3892
Remote Ground CT x Origin 1
0 to 16
---
1
F248
0 (None)
3893
Remote Ground CT x Origin 2
0 to 16
---
1
F248
0 (None)
3894
AC Bank Redundancy Type
0 to 2
---
1
F261
1 (Dependability
Biased)
3895
Remote Phase CT 1 Primary
1 to 65000
---
1
F001
1
3896
Remote Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
3897
Remote Ground CT 1 Primary
1 to 65000
---
1
F001
1
3898
Remote Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
3899
Remote Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
389A
Remote Phase VT 1 Secondary
25 to 240
---
0.1
F001
664
389B
Remote Phase VT 1 Ratio
1 to 24000
---
1
F060
1
389D
Remote Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
389E
Remote Auxiliary VT 1 Secondary
25 to 240
---
0.1
F001
664
389F
Remote Auxiliary VT 1 Ratio
1 to 24000
---
1
F060
1
38A1
...Repeated for Field Unit 2
38B2
...Repeated for Field Unit 3
38C3
...Repeated for Field Unit 4
38D4
...Repeated for Field Unit 5
38E5
...Repeated for Field Unit 6
Table B–10: MODBUS MEMORY MAP (Sheet 17 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание C70
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 452: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 1 OVERVIEW 8 THEORY OF OPERATION 8 ...
Страница 474: ...9 22 C70 Capacitor Bank Protection and Control System GE Multilin 9 4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 486: ...10 12 C70 Capacitor Bank Protection and Control System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 630: ...B 110 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 688: ...F 12 C70 Capacitor Bank Protection and Control System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...