7-4
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
TARGETS MENU
CHAPTER 7: COMMANDS AND TARGETS
7
SERVICE COMMAND
— Performs specific C30 service actions. Presently, there are two service actions available. Code
"20511" returns all settings to their factory default value. Code “101” is used to clear factory diagnostic information stored
in the non-volatile memory. If a code other than these two is entered, the command is ignored and no action is taken.
Various self-checking diagnostics are performed in the background while the C30 is running, and diagnostic information is
stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic
information is cleared before the C30 is shipped from the factory, the user can want to clear the diagnostic information for
themselves under certain circumstances. For example, you clear diagnostic information after replacement of hardware.
Once the diagnostic information is cleared, all self-checking variables are reset to their initial state and diagnostics restart
from scratch.
SAVE VOLATILE DATA
— Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
recent as possible instead of relying on the periodic timer to save the data.
7.1.5 Security
COMMANDS
SECURITY
With the CyberSentry option, this setting is available to enable or disable the following commands.
ADMINISTRATOR LOGOFF
— Selecting ‘Yes’ allows the Supervisor to forcefully logoff an administrator session.
ENGINEER LOGOFF
— Selecting ‘Yes’ allows the Supervisor to forcefully logoff an engineer session.
OPERATOR LOGOFF
— Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session.
CLEAR SECURITY DATA
— Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the
operands associated with the self-tests.
7.2 Targets menu
With the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command.
SECURITY
ADMINISTRATOR
LOGOFF: No
Range: Yes, No
ENGINEER
LOGOFF: No
Range: Yes, No
OPERATOR
LOGOFF: No
Range: Yes, No
CLEAR SECURITY DATA:
No
Range: Yes, No
TARGETS
PHASE TOC4
OP: A B -
Displayed only if targets for this element are active.
Example shown.
DIGITAL ELEMENT 48:
LATCHED
Displayed only if targets for this element are active.
Example shown.
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...