CHAPTER 5: SETTINGS
CONTROL ELEMENTS
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
5-161
5
The figure shows a general form of a PID regulator in the s domain.
PID 1 SAMPLE TIME:
0.05 s
Range: 0.05 to 30.00 s in steps of 0.01
PID 1 PROCESS
SIGNAL: Off
Range: Off, any FlexAnalog parameter
PID 1 SETPOINT
SIGNAL: 0.00
Range: -99999.99 to 99999.99 in steps of 0.01
PID 1 TRACKING SIGNAL:
Off
Range: Off, any FlexAnalog parameter
PID 1 PROPORTIONAL
GAIN: 1.00
Range: 0.01 to 100.00 in steps of 0.01
PID 1 SETPOINT
WEIGHTING: 1.00
Range: 0.01 to 1.00 in steps of 0.01
PID 1 INTEG. TIME
CONST.: 1.00 sec
Range: 0.00 to 600.00 s in steps of 0.01
PID 1 ANTIWINDUP:
Disabled
Range: Enabled, Disabled
PID 1 AW TIME CONST.:
1.00 sec
Range: 0.00 to 600.00 s in steps of 0.01
PID 1 DERIV. TIME
CONST.: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
PID 1 DERIVATIVE
LIMIT: 10
Range: 1 to 20 in steps of 1
PID 1 MAX:
10
Range: -10000 to 10000 in steps of 1
PID 1 MIN:
10
Range: -10000 to 10000 in steps of 1
PID 1 Tmin:
500 ms
Range: 100 to 1000 ms in steps of 1
PID 1 DEAD TIME:
1.00 sec
Range: 1 to 20 s in steps of 1
PID 1 BLK:
Off
Range: FlexLogic operand
PID 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
PID 1
EVENTS: Disabled
Range: Enabled, Disabled
The C30 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...