CHAPTER 5: SETTINGS
PRODUCT SETUP
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
5-105
5
The local and remote operation of each user-programmable pushbutton can be inhibited through the
PUSHBTN 1 LOCAL
and
PUSHBTN 1 REMOTE
settings, respectively. If local locking is applied, the pushbutton ignores set and reset commands
executed through the front panel pushbuttons. If remote locking is applied, the pushbutton ignores set and reset
commands executed through FlexLogic operands.
The locking functions are not applied to the autoreset feature. In this case, the inhibit function can be used in SBO control
operations to prevent the pushbutton function from being activated and ensuring “one-at-a-time” select operation.
The locking functions can also be used to prevent the accidental pressing of the front panel pushbuttons. The separate
inhibit of the local and remote operation simplifies the implementation of local/remote control supervision.
Pushbutton states can be logged by the event recorder and displayed as target messages. In latched mode, user-defined
messages can also be associated with each pushbutton and displayed when the pushbutton is on or changing to off.
PUSHBUTTON 1 FUNCTION
— This setting selects the characteristic of the pushbutton. If set to “Disabled,” the pushbutton is
not active and the corresponding FlexLogic operands (both “On” and “Off”) are de-asserted. If set to “Self-Reset,” the
control logic is activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically pressed or
virtually pressed via a FlexLogic operand assigned to the
PUSHBTN 1 SET
setting.
When in “Self-Reset” mode and activated locally, the pushbutton control logic asserts the “On” corresponding FlexLogic
operand as long as the pushbutton is being physically pressed, and after being released the deactivation of the operand is
delayed by the drop out timer. The “Off” operand is asserted when the pushbutton element is deactivated. If the
pushbutton is activated remotely, the control logic of the pushbutton asserts the corresponding “On” FlexLogic operand
only for the time period specified by the
PUSHBTN 1 DROP-OUT TIME
setting.
If set to “Latched,” the control logic alternates the state of the corresponding FlexLogic operand between “On” and “Off” on
each button press or by virtually activating the pushbutton (assigning set and reset operands). When in the “Latched”
mode, the states of the FlexLogic operands are stored in a non-volatile memory. If power supply is lost, the correct state of
the pushbutton is retained upon subsequent power up of the relay.
PUSHBTN 1 ID TEXT
— This setting specifies the top 20-character line of the user-programmable message and is intended to
provide ID information of the pushbutton. See the User-definable Displays section for instructions on how to enter
alphanumeric characters from the keypad.
PUSHBTN 1 ON TEXT
— This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is in the “on” position. See the User-definable Displays section for instructions on entering
alphanumeric characters from the keypad.
PUSHBTN 1 OFF TEXT
— This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is activated from the on to the off position and the
PUSHBUTTON 1 FUNCTION
is “Latched.”
This message is not displayed when the
PUSHBUTTON 1 FUNCTION
is “Self-reset” as the pushbutton operand status is
implied to be “Off” upon its release. The length of the “Off” message is configured with the
PRODUCT SETUP
DISPLAY
PROPERTIES
FLASH MESSAGE TIME
setting.
PUSHBTN 1 HOLD
— This setting specifies the time required for a pushbutton to be pressed before it is deemed active. This
timer is reset upon release of the pushbutton. Note that any pushbutton operation requires the pushbutton to be pressed a
minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer.
PUSHBTN 1 SET
— This setting assigns the FlexLogic operand serving to operate the pushbutton element and to assert
PUSHBUTTON 1 ON
operand. The duration of the incoming set signal must be at least 100 ms.
PUSHBTN 1 RESET
— This setting assigns the FlexLogic operand serving to reset pushbutton element and to assert
PUSHBUTTON 1 OFF
operand. This setting is applicable only if pushbutton is in latched mode. The duration of the incoming reset
signal must be at least 50 ms.
PUSHBTN 1 AUTORST
— This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable
only if the pushbutton is in the “Latched” mode.
PUSHBTN 1 AUTORST DELAY
— This setting specifies the time delay for automatic reset of the pushbutton when in the
latched mode.
The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the
pushbutton. This allows the user-programmable pushbuttons to properly operate during power cycling events and
various system disturbances that can cause transient assertion of the operating signals.
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...