5-104
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Figure 5-43: User-programmable pushbuttons (enhanced faceplate)
The following figure shows user-configurable pushbuttons for the standard faceplate.
Figure 5-44: User-programmable pushbuttons (standard faceplate)
Both the standard and enhanced faceplate pushbuttons can be custom labeled with a factory-provided template,
available online at
http://www.gegridsolutions.com/multilin
. The EnerVista software can also be used to create labels for
the enhanced faceplate.
Each pushbutton asserts its own “On” and “Off” FlexLogic operands (for example,
PUSHBUTTON 1 ON
and
PUSHBUTTON 1 OFF
).
These operands are available for each pushbutton and are used to program specific actions. If any pushbutton is active,
the
ANY PB ON
operand is asserted.
Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of the
corresponding pushbutton (on or off). However, each LED indicator can be assigned to any FlexLogic operand through the
PUSHBTN 1 LED CTL
setting.
The pushbuttons can be automatically controlled by activating the operands assigned to the
PUSHBTN 1 SET
(for latched
and self-reset mode) and
PUSHBTN 1 RESET
(for latched mode only) settings. The pushbutton reset status is declared when
the
PUSHBUTTON 1 OFF
operand is asserted. The activation and deactivation of user-programmable pushbuttons is dependent
on whether latched or self-reset mode is programmed.
•
Latched mode
— In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the
PUSHBTN 1 SET
setting or by directly pressing the associated front panel pushbutton. The pushbutton maintains the set
state until deactivated by the reset command or after a user-specified time delay. The state of each pushbutton is
stored in non-volatile memory and maintained through a loss of control power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the
PUSHBTN 1 RESET
setting or by directly pressing the associated active front panel pushbutton.
It can also be programmed to reset automatically through the
PUSHBTN 1 AUTORST
and
PUSHBTN 1 AUTORST DELAY
settings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if
control is not executed within a specified time period.
•
Self-reset mode
— In self-reset mode, a pushbutton remains active for the time it is pressed (the
pulse duration
) plus
the dropout time specified in the
PUSHBTN 1 DROP-OUT TIME
setting. If the pushbutton is activated via FlexLogic, the
pulse duration is specified by the
PUSHBTN 1 DROP-OUT TIME
only. The time the operand remains assigned to the
PUSHBTN 1 SET
setting has no effect on the pulse duration.
The pushbutton is reset (deactivated) in self-reset mode when the dropout delay specified in the
PUSHBTN 1 DROP-OUT
TIME
setting expires.
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...