5-86
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC 60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC 60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the C30 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the
control field of the response).
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-103
IEC103 INPUTS MEASURANDS
POINT 95 Input
Off
Range: FlexLogic operand
IEC103 INPUTS
MEASURANDS
ASDU 1
See below
ASDU 4
ASDU 1
ASDU 1 TYP:
9
Range: 3 or 9
ASDU 1 FUN:
0
Range: 0 to 255 in steps of 1
ASDU 1 INF:
0
Range: 0 to 255 in steps of 1
ASDU 1 SCAN TOUT:
0
Range: 0 to 1000 s in steps of 1
ASDU 1 ANALOG 1
Off
Range: FlexAnalog parameter
ASDU 1 ANALOG 1
FACTOR: 1.000
Range: 0.000 to 65.535 in steps of 0.001
ASDU 1 ANALOG 1
OFFSET: 0
Range: -32768 to 32767 in steps of 1
ASDU 1 ANALOG 9
Off
Range: FlexAnalog parameter
ASDU 1 ANALOG 9
FACTOR: 1.000
Range: 0.000 to 65.535 in steps of 0.001
ASDU 1 ANALOG 9
OFFSET: 0
Range: -32768 to 32767 in steps of 1
ASDU 4
ASDU 4 TYP:
9
Range: 3 or 9
ASDU 4 FUN:
0
Range: 0 to 255 in steps of 1
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...