CHAPTER 6: ACTUAL VALUES
STATUS
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
6-9
6
6.3.17.2 Slow exchange
ACTUAL VALUES
STATUS
EGD PROTOCOL STATUS
PRODUCER STATUS
SLOW EXCHANGE 1(2)
These values provide information for debugging an EGD network. The EGD signature and packet size for the slow EGD
exchanges display.
6.3.18 Teleprotection channel tests
ACTUAL VALUES
STATUS
TELEPROT CH TESTS
The status information for two channels is shown here.
CHANNEL 1 STATUS
— This represents the receiver status of each channel. If the value is “OK,” teleprotection is enabled and
data is being received from the remote terminal; If the value is “FAIL,” teleprotection enabled and data is not being received
from the remote terminal. If “n/a,” teleprotection is disabled.
CHANNEL 1 LOST PACKETS
— Data is transmitted to the remote terminals in data packets at a rate of two packets per cycle.
The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS
CLEAR RECORDS
menu.
VALIDITY OF CHANNEL CONFIGURATION
— This value displays the current state of the communications channel identification
check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the “FAIL” message
displays. The “N/A” value appears if the local relay ID is set to a default value of “0,” the channel is failed, or if the
teleprotection inputs/outputs are not enabled.
6.3.19 Remaining connection status
ACTUAL VALUES
STATUS
COMM STATUS REMAINING CONNECT
SLOW EXCHANGE 1
SLOW EXCHANGE 1
SIGNATURE: 0
SLOW EXCHANGE 1
DATA LENGTH: 0
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
Range: n/a, FAIL, OK
CHANNEL 1 LOST
PACKETS: 1
Range: 1 to 65535 in steps of 1
CHANNEL 2
STATUS: n/a
Range: n/a, FAIL, OK
CHANNEL 2 LOST
PACKETS: 1
Range: 1 to 65535 in steps of 1
VALIDITY OF CHANNEL
CONFIGURATION: FAIL
Range: n/a, FAIL, OK
COMM STATUS
REMAINING CONNECT
MMS TCP(max 5)
5
Range: 0 to 5
MODBUS TCP (max 4)
4
Range: 0 to 4
DNP TCP(max 2)
2
Range: 0 to 2
IEC-104 TCP(max 2)
2
Range: 0 to 2
SFTP (max 4)
4
Range: 0 to 4
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...