CHAPTER 5: SETTINGS
PRODUCT SETUP
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
5-101
5
5.3.10 User-programmable self-tests
SETTINGS
PRODUCT SETUP
USER-PROGRAMMALBE SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.
Most of the minor alarms can be disabled if so wanted.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7
for information on major and minor self-test alarms.
5.3.11 Control pushbuttons
SETTINGS
PRODUCT SETUP
CONTROL PUSHBUTTONS
CONTROL PUSHBUTTON 1(7)
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
The location of the control pushbuttons are shown in the following figures.
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
RxGOOSE OFF
FUNCTION: Enabled
Range: Disabled, Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
SFP MODULE FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
PTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
CONTROL
PUSHBUTTON 1
CONTROL PUSHBUTTN 1 ID
CTRL PB 1
Range: up to 20 alphanumeric characters
CONTROL PUSHBUTTON 1
FUNCTION: Disabled
Range: Disabled, Enabled
CONTROL PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...