CHAPTER 6: ACTUAL VALUES
STATUS
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
6-7
6
These values indicate the status of the first, second, and third Ethernet links.
6.3.14 Real time clock synchronizing
ACTUAL VALUES
STATUS
REAL TIME CLOCK SYNCHRONIZING
RTC SYNC SOURCE
actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, Other, and None, where "Other" means any less precise source (SNTP,
IEC 103, IEC 104, or DNP). An actual value displays when the relay includes the IEEE 1588 software option.
The
GRANDMASTER ID
is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
ACCURACY
is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
PORT 1…3 PTP STATE
is the present state of the port’s PTP clock. The PTP clock state is:
•
Disabled
is the port’s function setting is Disabled
•
No Signal
if enabled but no signal from an active master has been found and selected
•
Calibrating
if an active master has been selected but lock is not at present established
•
Synch’d (No Pdelay)
if the port is synchronized, but the peer delay mechanism is non-operational
•
Synchronized
if synchronized
PTP - IRIG-B DELTA
is the time difference, measured in nanoseconds, between the fractional seconds portion of the time
being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-
B time.
6.3.15 Direct inputs
ACTUAL VALUES
STATUS
DIRECT INPUTS
ETHERNET TER LINK
STATUS: Fail
Range: Fail, OK
REAL TIME CLOCK
SYNCHRONIZING
RTC SYNC SOURCE:
None
Range: see below
GRANDMASTER ID:
0X0000000000000000
Range: any 8 octet value
ACCURACY:
999999999 ns
Range: 0 to 999,999,999 ns
PORT 1 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PORT 2 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PORT 3 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PTP - IRIG-B DELTA:
500000000 ns
Range: -500,000,000 to +500,000,000 ns
DIRECT INPUTS
AVERATE MSG RETURN
TIME CH1: 0 ms
UNRETURNED MSG
COUNT CH1: 0
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...