5-106
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
PUSHBTN 1 REMOTE
— This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the operand
assigned to the
PUSHBTN 1 SET
or
PUSHBTN 1 RESET
settings.
PUSHBTN 1 LOCAL
— This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front panel
pushbuttons. This locking functionality is not applicable to pushbutton autoreset.
PUSHBTN 1 DROP-OUT TIME
— This setting applies only to “Self-Reset” mode and specifies the duration of the pushbutton
active status after the pushbutton has been released. When activated remotely, this setting specifies the entire activation
time of the pushbutton status; the length of time the operand remains on has no effect on the pulse duration. This setting
is required to set the duration of the pushbutton operating pulse.
PUSHBTN 1 LED CTL
— This setting assigns the FlexLogic operand serving to drive pushbutton LED. If this setting is “Off,” then
LED operation is directly linked to the
PUSHBUTTON 1 ON
operand.
PUSHBTN 1 MESSAGE
— If pushbutton message is set to “High Priority,” the message programmed in the
PUSHBTN 1 ID
and
PUSHBTN 1 ON TEXT
settings are displayed undisturbed as long as
PUSHBUTTON 1 ON
operand is asserted. The high priority
option is not applicable to the
PUSHBTN 1 OFF TEXT
setting.
This message can be temporary removed if any front panel keypad button is pressed. However, 10 seconds of keypad
inactivity restores the message if the
PUSHBUTTON 1 ON
operand is still active.
If the
PUSHBTN 1 MESSAGE
is set to “Normal,” the message programmed in the
PUSHBTN 1 ID
and
PUSHBTN 1 ON TEXT
settings
are displayed as long as
PUSHBUTTON 1 ON
operand is asserted, but not longer than time period specified by
FLASH MESSAGE
TIME
setting. After the flash time is expired, the default message or other active target message is displayed. The
instantaneous reset of the flash message is executed if any relay front panel button is pressed or any new target or
message becomes active.
The
PUSHBTN 1 OFF TEXT
setting is linked to
PUSHBUTTON 1 OFF
operand and displays in conjunction with
PUSHBTN 1 ID
only if
pushbutton element is in the “Latched” mode. The
PUSHBTN 1 OFF TEXT
message displays as “Normal” if the
PUSHBTN 1
MESSAGE
setting is “High Priority” or “Normal.”
PUSHBUTTON 1 EVENTS
— If this setting is enabled, each pushbutton state change is logged as an event into the event
recorder.
The figures show the user-programmable pushbutton logic.
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...