
5-62
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
in the integer result. The FlexElement Base Units table in the Settings > FlexLogic > FlexElements section later, which
tabulates the per-unit base value used by its pickup setting and implies the per-unit base used by other FlexAnalogs, can
be of use in selecting a value for the
RxGOOSE Analog1 PU
setting.
Some UR elements have requirements for the type of input operands, for instance current type or voltage type. These
elements assume that RxGOOSE Analog operands are of whatever type is necessary to meet these requirements.
The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 and a
PU base of 0.001 is 1.
When using RxGOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexElement
actual values is 2,140,000.000.
Reports
Navigate to
Settings > Product Setup > Communications > IEC 61850 > Reports
.
Report settings
Navigate to
Settings > Product Setup > Communications > IEC 61850 > Reports > Report Settings
.
ReportSettings rptID
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the RptID attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false. The RptID is the name of the report.
ReportSettings optFields
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the OptFlds attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings bufTime
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the BufTm attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings trgOps
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the TrgOps attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings intgPd
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the IntgPd attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
Buffered and unbuffered reports
Navigate to
Settings > Product Setup > Communications > IEC 61850 > Reports > Buffered Reports
or
Unbuffered
Reports
.
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...