6-10
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
STATUS
CHAPTER 6: ACTUAL VALUES
6
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
MMS TCP
— The number of IEC 61850 connections remaining.
6.3.20 Parallel Redundancy Protocol (PRP)
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks.
ACTUAL VALUES
STATUS
PRP STATUS
Total Received Port A
is a counter for total messages received (either from DANPs or from SANs) on Port A.
Total Received Port B
is a counter for total messages received (either from DANPs or from SANs) on Port B.
Total Errors
is a counter for total messages received with an error (bad port code, frame length too short).
Mismatches Port A
is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
Mismatches Port B
is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
6.3.21 TxGOOSE status
ACTUAL VALUES
STATUS
TxGOOSE STATUS
PRP STATUS
Total Rx Port A:
Range: 0 to 4G, blank if PRP disabled
Total Rx Port B:
Range: 0 to 4G, blank if PRP disabled
Mismatches Port A:
Range: 0 to 4G, blank if PRP disabled
Mismatches Port B:
Range: 0 to 4G, blank if PRP disabled
Total Errors:
Range: 0 to 4G, blank if PRP disabled
The C30 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
TxGOOSE STATUS
R-TxGOOSE 1
ARP: Off
Range: On, Off
R-TxGOOSE 16
ARP: Off
Range: On, Off
The C30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...