CHAPTER 5: SETTINGS
PRODUCT SETUP
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
5-89
5
Commands are received as General Command (Type Identification 20). The user can configure the action to perform when
an ASDU command comes.
A list of available mappings is provided on the C30. This includes 64 virtual inputs (see the following table). The ON and OFF
for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-12: Commands mapping table
5.3.5 Modbus user map
SETTINGS
PRODUCT SETUP
MODBUS USER MAP
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the address
in the
ADDRESS
line (converted from hex to decimal format). The corresponding value (if programmed) displays in the
VALUE
line. A value of “0” in subsequent register
ADDRESS
lines automatically returns values for the previous
ADDRESS
lines
incremented by 1. An address value of “0” in the initial register means “none” and values of “0” display for all registers.
Different
ADDRESS
values can be entered as required in any of the register positions.
The UR Family Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser;
enter the IP address of the C30 in a web browser and click the option.
5.3.6 Real-time clock
5.3.6.1 Menu
SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
COMMAND 31 ON:
Off
Range: Virtual input
COMMAND 31 OFF:
Off
Range: Virtual input
Description
Value
Off
0
Virtual Input 1
1
Virtual Input 2
2
...
...
Virtual Input 64
64
MODBUS USER MAP
ADDRESS 1: 0
VALUE: 0
Range: 0 to 65535 in steps of 1
ADDRESS 256:
0
VALUE: 0
Range: 0 to 65535 in steps of 1
REAL TIME
CLOCK
SYNCRONIZING SOURCE:
None
Range: None, PP/IRIG-B/PTP/Other, IRIG-B/PP/PTP/
Other, PP/PTP/IRIG-B/Other
REAL TIME CLOCK
EVENTS: Disabled
Range: Enabled, Disabled
IRIG-B SIGNAL TYPE:
None
Range: None, DC Shift, Amplitude Modulated
PRECISION TIME
PROTOCOL (1588)
See below
Содержание C30
Страница 12: ...1 4 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 282: ...5 126 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL SYSTEM SETUP CHAPTER 5 SETTINGS 5 Figure 5 56 Disconnect switch logic...
Страница 354: ...6 16 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6...
Страница 398: ...C 6 C30 CONTROLLER SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C...
Страница 406: ...iv C30 CONTROLLER SYSTEM INSTRUCTION MANUAL ABBREVIATIONS...