GE Multilin
L60 Line Phase Comparison System
B-37
APPENDIX B
B.4 MEMORY MAPPING
B
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 Modules)
63C0
Negative Sequence Instantaneous OC 1 Function
0 to 1
---
1
F102
0 (Disabled)
63C1
Negative Sequence Instantaneous OC 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
63C2
Negative Sequence Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
63C3
Negative Sequence Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
63C4
Negative Sequence Instantaneous OC 1 Reset Delay
0 to 600
s
0.01
F001
0
63C5
Negative Sequence Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
63C7
Negative Sequence Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
63C8
Negative Sequence Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
63C9
Reserved (8 items)
0 to 1
---
1
F001
0
63D1
...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting) (3 Modules)
6440
Negative Sequence Overvoltage Function
0 to 1
---
1
F102
0 (Disabled)
6441
Negative Sequence Overvoltage Source
0 to 5
---
1
F167
0 (SRC 1)
6442
Negative Sequence Overvoltage Pickup
0 to 1.25
pu
0.001
F001
300
6443
Negative Sequence Overvoltage Pickup Delay
0 to 600
s
0.01
F001
50
6444
Negative Sequence Overvoltage Reset Delay
0 to 600
s
0.01
F001
50
6445
Negative Sequence Overvoltage Block
0 to 4294967295
---
1
F300
0
6447
Negative Sequence Overvoltage Target
0 to 2
---
1
F109
0 (Self-reset)
6448
Negative Sequence Overvoltage Events
0 to 1
---
1
F102
0 (Disabled)
6449
...Repeated for module number 2
6452
...Repeated for module number 3
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
0 to 1
---
1
F102
0 (Disabled)
65C1
Power Swing Detect Source
0 to 5
---
1
F167
0 (SRC 1)
65C2
Power Swing Detect Mode
0 to 1
---
1
F513
0 (Two Step)
65C3
Power Swing Detect Supervision
0.05 to 30
pu
0.001
F001
600
65C4
Power Swing Detect Forward Reach
0.1 to 500
ohms
0.01
F001
5000
65C5
Power Swing Detect Forward RCA
40 to 90
degrees
1
F001
75
65C6
Power Swing Detect Reverse Reach
0.1 to 500
ohms
0.01
F001
5000
65C7
Power Swing Detect Reverse RCA
40 to 90
degrees
1
F001
75
65C8
Power Swing Detect Outer Limit Angle
40 to 140
degrees
1
F001
120
65C9
Power Swing Detect Middle Limit Angle
40 to 140
degrees
1
F001
90
65CA
Power Swing Detect Inner Limit Angle
40 to 140
degrees
1
F001
60
65CB
Power Swing Detect Delay 1 Pickup
0 to 65.535
s
0.001
F001
30
65CC
Power Swing Detect Delay 1 Reset
0 to 65.535
s
0.001
F001
50
65CD
Power Swing Detect Delay 2 Pickup
0 to 65.535
s
0.001
F001
17
65CE
Power Swing Detect Delay 3 Pickup
0 to 65.535
s
0.001
F001
9
65CF
Power Swing Detect Delay 4 Pickup
0 to 65.535
s
0.001
F001
17
65D0
Power Swing Detect Seal In Delay
0 to 65.535
s
0.001
F001
400
65D1
Power Swing Detect Trip Mode
0 to 1
---
1
F514
0 (Delayed)
65D2
Power Swing Detect Block
0 to 4294967295
---
1
F300
0
65D4
Power Swing Detect Target
0 to 2
---
1
F109
0 (Self-reset)
65D5
Power Swing Detect Event
0 to 1
---
1
F102
0 (Disabled)
65D6
Power Swing Detect Shape
0 to 1
---
1
F085
0 (Mho Shape)
65D7
Power Swing Detect Quad Forward Middle
0.1 to 500
ohms
0.01
F001
6000
65D8
Power Swing Detect Quad Forward Outer
0.1 to 500
ohms
0.01
F001
7000
65D9
Power Swing Detect Quad Reverse Middle
0.1 to 500
ohms
0.01
F001
6000
65DA
Power Swing Detect Quad Reverse Outer
0.1 to 500
ohms
0.01
F001
7000
65DB
Power Swing Detect Outer Right Blinder
0.1 to 500
ohms
0.01
F001
10000
65DC
Power Swing Detect Outer Left Blinder
0.1 to 500
ohms
0.01
F001
10000
65DD
Power Swing Detect Middle Right Blinder
0.1 to 500
ohms
0.01
F001
10000
65DE
Power Swing Detect Middle Left Blinder
0.1 to 500
ohms
0.01
F001
10000
65DF
Power Swing Detect Inner Right Blinder
0.1 to 500
ohms
0.01
F001
10000
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...