GE Multilin
L60 Line Phase Comparison System
5-165
5 SETTINGS
5.5 GROUPED ELEMENTS
5
The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. When set to “Non-directional”, the mho function becomes an offset
mho with the reverse reach controlled independently from the forward reach, and all the directional characteristics
removed.
The phase quadrilateral distance function is comprised of a reactance characteristic, right and left blinders, and 100%
memory-polarized directional and current supervising characteristics. When set to “Non-directional”, the quadrilateral func-
tion applies a reactance line in the reverse direction instead of the directional comparators. Refer to Chapter 8 for additional
information.
Each phase distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1.
The
SIGNAL SOURCE
setting (common for the distance elements of all zones as entered under
SETTINGS
GROUPED
ELEMENTS
SETTING GROUP 1(6)
DISTANCE
).
2.
The
MEMORY DURATION
setting (common for the distance elements of all zones as entered under
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
).
The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in chapter 8:
Theory of operation
.
Although all zones can be used as either instantaneous elements (pickup [
PKP
] and dropout [
DPO
] FlexLogic operands) or
time-delayed elements (operate [
OP
] FlexLogic operands), only zone 1 is intended for the instantaneous under-reaching
tripping mode.
MESSAGE
PHS DIST Z1
COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1
DIR RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1
DIR COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1 QUAD
RGT BLD: 10.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1 QUAD
RGT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
PHS DIST Z1 QUAD
LFT BLD: 10.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1 QUAD
LFT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
PHS DIST Z1
SUPV: 0.200 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
PHS DIST Z1 VOLT
LEVEL: 0.000 pu
Range: 0.000 to 5.000 pu in steps of 0.001
MESSAGE
PHS DIST Z1
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
PHS DIST Z1 BLK:
Off
Range: FlexLogic operand
MESSAGE
PHS DIST Z1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
PHS DIST Z1
EVENTS: Disabled
Range: Disabled, Enabled
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...