5 SETTINGS
5.5 GROUPED ELEMENTS
5
g) NEGATIVE-SEQUENCE OVERCURRENT FAULT DETECTION
PATH: SETTINGS
GROUPED ELEMENTS
PHASE COMPARISON ELEMENTS
ADVANCED FAULT DETECTORS
NEGATIVE-SEQUENCE CURRENT
The negative-sequence overcurrent advanced fault detector element responds to the increment of the magnitude of the
negative-sequence current over a specified threshold. Thresholds are provided for low-set control of keying and high-set
operation control of tripping.
The following settings are available.
•
NEG SEQ I_2 FD FUNCTION
: This setting enables or disables the negative-sequence overcurrent fault detection.
Note that all fault detectors operate in parallel with the 87PC function. To effectively disable the overcurrent fault detec-
tors under the main 87PC menu, set their threshold very high.
•
NEG SEQ I_2 FDL PICKUP
: This setting specifies the pickup of the low-set stage of the element used to control the
key operation. The nominal current of the phase CT bank of the relay is 1 pu.
•
NEG SEQ I_2 FDH PICKUP
: This setting specifies the pickup of the high-set stage of the element used to control the
trip operation. The nominal current of the phase CT bank of the relay is 1 pu.
•
NEG SEQ I_2 BLK
: The fault detector is hard-wired to the 87PC scheme. It can be disabled permanently using the
function setting or blocked temporarily with this setting. This setting selects a FlexLogic operand that blocks this fault
detector when asserted.
•
NEG SEQ I_2 FD TARGET
: This setting controls targets of the negative-sequence overcurrent advanced fault detector
function. These targets operate independently from the 87PC targets.
•
NEG SEQ I_2 FD EVENTS
: This setting controls event recording of the negative-sequence overcurrent advanced fault
detector function. These events are logged independently from the 87PC events.
Figure 5–57: NEGATIVE-SEQUENCE OVERCURRENT ADVANCED FAULT DETECTOR LOGIC
NEGATIVE-SEQUENCE
CURRENT
NEG SEQ I_2 FD
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
NEG SEQ I_2 FDL
PICKUP: 0.10 pu
Range: 0.02 to 5.00 pu in steps of 0.01
MESSAGE
NEG SEQ I_2 FDH
PICKUP: 0.50 pu
Range: 0.05 to 15.00 pu in steps of 0.01
MESSAGE
NEG SEQ I_2 BLK:
Off
Range: FlexLogic operand
MESSAGE
NEG SEQ I_2 FD
TARGET: Self-reset
Range: Self-Reset, Latched, Disabled
MESSAGE
NEG SEQ I_2 FD
EVENTS: Disabled
Range: Disabled, Enabled
Hardwired to the
87PC function
To square pulse
and transmit logic
SETTINGS
Enabled = 1
NEG SEQ I_2 FD FUNCTION
Off = 0
NEG SEQ I_2 BLOCK
AND
FAST MEASUREMENTS
Negative-sequence
current I_2
F1 PHASE CT BANK
L1 PHASE CT BANK
Negative-sequence
current I_2
Σ
SETTINGS
NEG SEQ I_2 FDH PICKUP
RUN
NEG SEQ I_2 FDL PICKUP
> (FDL PICKUP) / 4
> (FDH PICKUP) / 4
> (FDL PICKUP) / 4
> (FDH PICKUP) / 4
> FDL PICKUP
> FDH PICKUP
OR
OR
AND
AND
FLEXLOGIC OPERANDS
87PC I_2 FDL OP
87PC I_2 FDH OP
831030A2.CDR
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...