5.6 CONTROL ELEMENTS
5 SETTINGS
5
The thermal overload protection element corresponds to the IEC 255-8 standard and is used to detect thermal overload
conditions in protected power system elements. Choosing an appropriate time constant element can be used to protect dif-
ferent elements of the power system. The cold curve characteristic is applied when the previous averaged load current over
the last 5 cycles is less than 10% of the base current. If this current is greater or equal than 10% than the base current, then
the hot curve characteristic is applied.
The IEC255-8 cold curve is defined as follows:
(EQ 5.27)
The IEC255-8 hot curve is defined as follows:
(EQ 5.28)
In the above equations,
•
t
op
= time to operate
•
τ
op
= thermal protection trip time constant
•
I
= measured overload RMS current
•
I
p
= measured load RMS current before overload occurs
•
k
= IEC 255-8 k-factor applied to
I
B
, defining maximum permissible current above nominal current
•
I
B
= protected element base (nominal) current
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x I
B
) is limited to 8, even when real-
istically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
(EQ 5.29)
In the above equation,
•
τ
rst
= thermal protection trip time constant
•
T
min
is a minimum reset time setting
t
op
op
I
2
I
2
kI
B
2
–
--------------------------
ln
=
t
op
op
I
2
I
p
2
–
I
2
kI
B
2
–
--------------------------
ln
=
t
rst
rst
kI
B
2
I
2
kI
B
2
–
-----------------------------
ln
T
min
+
=
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...