Example:
Administrative functions can be segmented away from common operator functions, or engineering type access,
all of which are defined by separate roles, as shown in the following figure, so that access of UR devices by multiple per-
sonnel within a substation is allowed. Permission for each role are outlined in the next section.
Figure 2–3: CYBERSENTRY USER ROLES
There are two types of authentication supported by CyberSentry that can be used to access the UR device:
•
Device Authentication (local UR device authenticates)
•
Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the
associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attribut-
able.
In cases where user attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information are displayed in plain text by the EnerVista software or UR device, nor are they ever
transmitted without cryptographic protection.
CYBERSENTRY USER ROLES
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means that the EnerVista software allows for access to functionality based on the user’s logged in
role.
Example:
Observer cannot write any settings.
The table lists the roles that are supported and their corresponding capabilities.
Table 2–3: PERMISSIONS BY USER ROLE FOR CYBERSENTRY
Roles
Administrator
Engineer
Operator
Supervisor
Observer
Complete access
Complete access
except for
CyberSentry
Security
Command
menu
Authorizes
writing
Default role
Device Definition
R
R
R
R
R
Settings
|------------
Product Setup
|--------------- Security (CyberSentry)
RW
R
R
R
R
|--------------- Supervisory
see table notes
R
R
see table notes
R
|--------------- Display Properties
RW
RW
R
R
R
842838A2.CDR
Administrator
Engineer
Supervisor
Operator
Observer
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...