GE Multilin
L60 Line Phase Comparison System
5-121
5 SETTINGS
5.4 FLEXLOGIC
5
ELEMENT:
Auxiliary
undervoltage
AUX UV1 PKP
AUX UV1 DPO
AUX UV1 OP
Auxiliary undervoltage element has picked up
Auxiliary undervoltage element has dropped out
Auxiliary undervoltage element has operated
AUX UV2 to AUX UV3
Same set of operands as shown for AUX UV1
ELEMENT
Breaker flashover
BKR 1 FLSHOVR PKP A
BKR 1 FLSHOVR PKP B
BKR 1 FLSHOVR PKP C
BKR 1 FLSHOVR PKP
BKR 1 FLSHOVR OP A
BKR 1 FLSHOVR OP B
BKR 1 FLSHOVR OP C
BKR 1 FLSHOVR OP
BKR 1 FLSHOVR DPO A
BKR 1 FLSHOVR DPO B
BKR 1 FLSHOVR DPO C
BKR 1 FLSHOVR DPO
Breaker 1 flashover element phase A has picked up
Breaker 1 flashover element phase B has picked up
Breaker 1 flashover element phase C has picked up
Breaker 1 flashover element has picked up
Breaker 1 flashover element phase A has operated
Breaker 1 flashover element phase B has operated
Breaker 1 flashover element phase C has operated
Breaker 1 flashover element has operated
Breaker 1 flashover element phase A has dropped out
Breaker 1 flashover element phase B has dropped out
Breaker 1 flashover element phase C has dropped out
Breaker 1 flashover element has dropped out
BKR 2 FLSHOVR...
Same set of operands as shown for BKR 1 FLSHOVR
ELEMENT:
Breaker arcing
BKR ARC 1 OP
BKR ARC 2 OP
Breaker arcing current 1 has operated
Breaker arcing current 2 has operated
ELEMENT
Breaker failure
BKR FAIL 1 RETRIPA
BKR FAIL 1 RETRIPB
BKR FAIL 1 RETRIPC
BKR FAIL 1 RETRIP
BKR FAIL 1 T1 OP
BKR FAIL 1 T2 OP
BKR FAIL 1 T3 OP
BKR FAIL 1 TRIP OP
Breaker failure 1 re-trip phase A (only for 1-pole schemes)
Breaker failure 1 re-trip phase B (only for 1-pole schemes)
Breaker failure 1 re-trip phase C (only for 1-pole schemes)
Breaker failure 1 re-trip 3-phase
Breaker failure 1 timer 1 is operated
Breaker failure 1 timer 2 is operated
Breaker failure 1 timer 3 is operated
Breaker failure 1 trip is operated
BKR FAIL 2...
Same set of operands as shown for BKR FAIL 1
ELEMENT:
Breaker control
BREAKER 1 OFF CMD
BREAKER 1 ON CMD
BREAKER 1
A BAD ST
BREAKER 1
A INTERM
BREAKER 1
A CLSD
BREAKER 1
A OPEN
BREAKER 1
B BAD ST
BREAKER 1
B INTERM
BREAKER 1
B CLSD
BREAKER 1
B OPEN
BREAKER 1
C BAD ST
BREAKER 1
C INTERM
BREAKER 1
C CLSD
BREAKER 1
C OPEN
BREAKER 1 BAD STATUS
BREAKER 1 CLOSED
BREAKER 1 OPEN
BREAKER 1 DISCREP
BREAKER 1 TROUBLE
BREAKER 1 MNL CLS
BREAKER 1 TRIP A
BREAKER 1 TRIP B
BREAKER 1 TRIP C
BREAKER 1 ANY P OPEN
BREAKER 1 ONE P OPEN
BREAKER 1 OOS
Breaker 1 open command initiated
Breaker 1 close command initiated
Breaker 1 phase A bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase A is closed
Breaker 1 phase A is open
Breaker 1 phase B bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Breaker 1 phase B intermediate status is detected (transition from one
position to another)
Breaker 1 phase B is closed
Breaker 1 phase B is open
Breaker 1 phase C bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Breaker 1 phase C intermediate status is detected (transition from one
position to another)
Breaker 1 phase C is closed
Breaker 1 phase C is open
Breaker 1 bad status is detected on any pole
Breaker 1 is closed
Breaker 1 is open
Breaker 1 has discrepancy
Breaker 1 trouble alarm
Breaker 1 manual close
Breaker 1 trip phase A command
Breaker 1 trip phase B command
Breaker 1 trip phase C command
At least one pole of breaker 1 is open
Only one pole of breaker 1 is open
Breaker 1 is out of service
BREAKER 2...
Same set of operands as shown for BREAKER 1
ELEMENT:
CT fail
CT FAIL PKP
CT FAIL OP
CT fail has picked up
CT fail has dropped out
ELEMENT:
Digital counters
Counter 1 HI
Counter 1 EQL
Counter 1 LO
Digital counter 1 output is ‘more than’ comparison value
Digital counter 1 output is ‘equal to’ comparison value
Digital counter 1 output is ‘less than’ comparison value
Counter 2 to Counter 8
Same set of operands as shown for Counter 1
Table 5–16: L60 FLEXLOGIC OPERANDS (Sheet 2 of 9)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...