GE Multilin
L60 Line Phase Comparison System
B-57
APPENDIX B
B.4 MEMORY MAPPING
B
B23C
...Repeated for Received Analog 23
B23E
...Repeated for Received Analog 24
B240
...Repeated for Received Analog 25
B242
...Repeated for Received Analog 26
B244
...Repeated for Received Analog 27
B246
...Repeated for Received Analog 28
B248
...Repeated for Received Analog 29
B24A
...Repeated for Received Analog 30
B24C
...Repeated for Received Analog 31
B24E
...Repeated for Received Analog 32
IEC 61850 Configurable Report Settings (Read/Write Setting)
B290
IEC 61850 configurable reports dataset items (64 items)
0 to 848
---
1
F615
0 (None)
Wattmetric Ground Fault Settings (read/write grouped, 5 Modules)
B300
Wattmetric ground fault 1 function
0 to 1
---
1
F102
0 (Disabled)
B301
Wattmetric ground fault 1 source
0 to 5
---
1
F167
0 (SRC 1)
B302
Wattmetric ground fault 1 voltage
0 to 1
---
1
F234
0 (Calculated VN)
B303
Wattmetric ground fault 1 overvoltage pickup
0.02 to 3.00
pu
0.01
F001
20
B304
Wattmetric ground fault 1 current
0 to 1
---
1
F235
0 (Calculated IN)
B305
Wattmetric ground fault 1 overcurrent pickup
0.002 to 30.000
pu
0.001
F001
60
B306
Wattmetric ground fault 1 overcurrent pickup delay
0 to 600
s
0.01
F001
20
B307
Wattmetric ground fault 1 power pickup
0.001 to 1.2
pu
0.001
F001
100
B308
Wattmetric ground fault 1 ECA
0 to 360
° Lag
1
F001
0
B309
Wattmetric ground fault 1 power pickup delay
0 to 600
s
0.01
F001
20
B30A
Wattmetric ground fault 1 curve
0 to 5
---
1
F236
0 (Definite Time)
B30B
Wattmetric ground fault 1 multiplier
0.01 to 2
s
0.01
F001
100
B30C
Wattmetric ground fault 1 block
0 to 65535
---
1
F300
0
B30E
Wattmetric ground fault 1 target
0 to 2
---
1
F109
0 (Self-reset)
B30F
Wattmetric ground fault 1 events
0 to 1
---
1
F102
0 (Disabled)
B310
Wattmetric ground fault 1 reference power
0.001 to 1.2
pu
0.001
F001
500
B311
Wattmetric ground fault x Reserved
0 to 1
---
1
F001
0
B312
...Repeated for wattmetric ground fault 2
B324
...Repeated for wattmetric ground fault 3
B336
...Repeated for wattmetric ground fault 4
B348
...Repeated for wattmetric ground fault 5
Wattmetric Ground Fault Actual Values (Read Only) (5 Modules)
B360
Wattmetric ground fault 1 operating power
0 to 999999.999
W
0.001
F060
0
B362
...Repeated for wattmetric ground fault 2
B364
...Repeated for wattmetric ground fault 3
B366
...Repeated for wattmetric ground fault 4
B368
...Repeated for wattmetric ground fault 5
IEC 61850 XSWI Configuration (Read/Write Setting) (24 Modules)
B370
Flexlogic Operand for IEC 61850 XSWI.ST.Loc Status
0 to 4294967295
---
1
F300
0
IEC 61850 XSWI Configuration (Read/Write Command) (24 Modules)
B372
Command to Clear XSWI OpCnt (Operation Counter)
0 to 1
---
1
F126
0 (No)
B373
...Repeated for module number 2
B376
...Repeated for module number 3
B379
...Repeated for module number 4
B37C
...Repeated for module number 5
B37F
...Repeated for module number 6
B382
...Repeated for module number 7
B385
...Repeated for module number 8
B388
...Repeated for module number 9
B38B
...Repeated for module number 10
B38E
...Repeated for module number 11
Table B–10: MODBUS MEMORY MAP (Sheet 49 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...