GE Multilin
L60 Line Phase Comparison System
B-35
APPENDIX B
B.4 MEMORY MAPPING
B
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Phase Comparison Negative Sequence Voltage (Read/Write Grouped Setting)
6070
Negative Sequence Voltage FD Function
0 to 1
---
1
F102
0 (Disabled)
6071
Negative Sequence Voltage FD Impedance
0 to 100
%
0.1
F001
100
6072
Negative Sequence Voltage FDL Pickup
0.005 to 3
pu
0.001
F001
10
6073
Negative Sequence Voltage FDH Pickup
0.005 to 3
pu
0.001
F001
50
6074
Negative Sequence Voltage FD Block
0 to 4294967295
---
1
F300
0
6076
Negative Sequence Voltage FD Target
0 to 2
---
1
F109
0 (Self-reset)
6077
Negative Sequence Voltage FD Events
0 to 1
---
1
F102
0 (Disabled)
Phase Comparison Negative Sequence Current ROC (Read/Write Grouped Setting)
6080
Negative Sequence di/dt FD Function
0 to 1
---
1
F102
0 (Disabled)
6081
Negative Sequence di/dt FDL Pickup
0.01 to 5
pu
0.01
F001
10
6082
Negative Sequence di/dt FDL Seal-In
0 to 10
s
0.001
F001
600
6083
Negative Sequence di/dt FDH Pickup
0.01 to 5
pu
0.01
F001
50
6084
Negative Sequence di/dt FDH Seal-In
0 to 10
s
0.001
F001
200
6085
Negative Sequence di/dt FDH Supv
0 to 4294967295
---
1
F300
0
6087
Negative Sequence di/dt FD Block
0 to 4294967295
---
1
F300
0
6089
Negative Sequence di/dt FD Target
0 to 2
---
1
F109
0 (Self-reset)
608A
Negative Sequence di/di FD Events
0 to 1
---
1
F102
0 (Disabled)
Phase Comparison: Rate of Change of Positive-Sequence Current Settings (Read/Write, Grouped)
6092
Positive-sequence Current Rate of Change Function
0 to 1
---
1
F102
0 (Disabled)
6093
Positive-sequence Current Rate of Change Low Pickup
0.01 to 5
pu
0.01
F001
10
6094
Positive-sequence Current Rate of Change Low Seal-in
0 to 10
s
0.001
F001
600
6095
Positive-sequence Current Rate of Change High Pickup
0.01 to 5
pu
0.01
F001
50
6096
Positive-sequence Current Rate of Change High Seal-in
0 to 10
s
0.001
F001
200
6097
Positive-sequence Current Rate of Change Supervision
0 to 4294967295
---
1
F300
0
6099
Positive-sequence Current Rate of Change Block
0 to 4294967295
---
1
F300
0
609B
Positive-sequence Current Rate of Change Events
0 to 1
---
1
F102
0 (Disabled)
609C
Positive-sequence Current Rate of Change Target
0 to 2
---
1
F109
0 (Self-reset)
Phase Comparison Negative-sequence Current Fault Detector (Read/Write Grouped Settings)
60A0
Negative-sequence Current Fault Detector Function
0 to 1
---
1
F102
0 (Disabled)
60A1
Negative-sequence Current Fault Detector Low Pickup
0.02 to 5
pu
0.01
F001
10
60A2
Negative-sequence Current Fault Detector High Pickup
0.05 to 15
pu
0.01
F001
50
60A3
Negative-sequence Current Fault Detector Block
0 to 4294967295
---
1
F300
0
60A5
Negative-sequence Current Fault Detector Target
0 to 2
---
1
F109
0 (Self-reset)
60A6
Negative-sequence Current Fault Detector Events
0 to 1
---
1
F102
0 (Disabled)
Phase Comparison Positive-sequence Current Fault Detector (Read/Write Grouped Settings)
60A8
Positive-sequence Current Fault Detector Function
0 to 1
---
1
F102
0 (Disabled)
60A9
Positive-sequence Current Fault Detector Low Pickup
0.02 to 5
pu
0.01
F001
50
60AA
Positive-sequence Current Fault Detector High Pickup
0.05 to 15
pu
0.01
F001
75
60AB
Positive-sequence Current Fault Detector Block
0 to 4294967295
---
1
F300
0
60AD
Positive-sequence Current Fault Detector Target
0 to 2
---
1
F109
0 (Self-reset)
60AE
Positive-sequence Current Fault Detector Events
0 to 1
---
1
F102
0 (Disabled)
Phase Comparison Open Breaker Keying (Read/Write Grouped Setting)
60C0
Open Breaker Keying
0 to 1
---
1
F102
0 (Disabled)
60C1
Breaker 1 Auxiliary Contact
0 to 4294967295
---
1
F300
0
60C3
Breaker 1 Supervision Element
0 to 4294967295
---
1
F300
0
60C5
Breaker 2 Auxiliary Contact
0 to 4294967295
---
1
F300
0
60C7
Breaker 2 Supervision Element
0 to 4294967295
---
1
F300
0
60C9
Weak-Infeed Keying
0 to 4294967295
---
1
F300
0
60CB
Supervision Element
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 27 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...