GE Multilin
L60 Line Phase Comparison System
5-109
5 SETTINGS
5.3 SYSTEM SETUP
5
•
SWITCH 1 OPEN:
This setting selects an operand that creates a programmable signal to operate a contact output to
open disconnect switch 1.
•
SWITCH 1 BLK OPEN
: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWITCH 1 CLOSE:
This setting selects an operand that creates a programmable signal to operate a contact output to
close disconnect switch 1.
•
SWITCH 1 BLK CLOSE
: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWTCH 1
A/3P CLSD:
This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 89/a status input to create a logic 1 when
the disconnect switch is closed. If the
SWITCH 1 MODE
setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the
SWITCH 1
B
and
SWITCH 1
C
settings select operands to
track phases B and C, respectively.
•
SWTCH 1
A/3P OPND:
This setting selects an operand, usually a contact input, that should be a normally-closed 89/
b status input to create a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available,
then an inverted 89/a status signal can be used.
•
SWITCH 1
B CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
•
SWITCH 1
B OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
•
SWITCH 1
C CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
•
SWITCH 1
C OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
•
SWITCH 1 Toperate
: This setting specifies the required interval to overcome transient disagreement between the 89/a
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the
SWITCH 1 BAD STATUS
FlexLogic operand is asserted from alarm or blocking purposes.
•
SWITCH 1 ALARM DELAY:
This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the L60 is in “Programmed” mode and not in the local control mode.
NOTE
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...