Revision 14
109
August 02, 2019
5.10.4.4 Differences between the H
2
S/Total Sulfur Tabs
and the Calibration/Reference/Zero Gas Tabs
The H
2
S/Total Sulfur tabs and the Calibration/Reference/Zero Gas Tabs are quite similar in
format, but the following differences between the two sets of tabs should be noted.
•
Cal Gas Concentration
- indicates the concentration of H
2
S or total sulfur in the
Calibration, Reference and Zero gas.
•
The Calibration and Zero Tabs do not include the
Stream Calibration Used
field.
•
The
Alarms
field contain only the
High Alarm Enable
and
% Deviation Enable
options.
•
Runs to Average
- indicates the number of consecutive runs to be averaged to obtain
the concentration reading. The Calibration, Reference and Zero gas runs have the ability
to average the concentration reading over a number of gas runs (the H2S and Total
Sulfur tabs do not have this field because the concentration is displayed after each
analysis).
•
Consecutive Runs
- This field tells the analyzer how many times to run the Gas run
before switching to the next run in the run queue. If no other run is enabled and it is set
up in the Automatic Sequence under the sequence tab, the analyzer will simply continue
running until another run is triggered either conditionally or scheduled. By default, this
field is set to 1. The
H2S Run for Stream 1
is setup to run continuously in the automatic
sequence under the
Sequencer
tab.
Содержание ProTech903
Страница 2: ......
Страница 96: ...Revision 14 96 August 02 2019 Figure 5 19 Event Log...
Страница 122: ...Revision 14 122 August 02 2019 Figure 5 38 Typical Modicon with Floating Point List...
Страница 124: ...Revision 14 124 August 02 2019 Figure 5 40 Expanded Modbus Nodes...
Страница 167: ...Revision 14 167 August 02 2019 Figure 9 1 DC Power Wiring Diagram Figure 9 2 AC Power Wiring Diagram...
Страница 168: ...Revision 14 168 August 02 2019 Figure 9 3 Total Sulfur Wiring Diagram Figure 9 4 AC DC Power Wiring Diagram...
Страница 169: ...Revision 14 169 August 02 2019 Figure 9 5 Solenoid Drivers Wiring Diagram Figure 9 6 Relays Wiring Diagram...
Страница 173: ...Revision 14 173 August 02 2019 Figure 9 13 Isolated RS 485 Port Figure 9 14 P17 RS232 Port to Ethernet Cable...
Страница 175: ...Revision 14 175 August 02 2019 Figure 9 17 Non Isolated 4 20 mA Inputs...
Страница 190: ...Revision 14 190 August 02 2019...