© Fulton Group N.A., Inc. 2021
3-26
OPERATION
ModSyncSE-User-Manual-211020
SECTION 3
!
WARNING
This manual is provided as a
guide to the correct operation and
maintenance of your equipment,
and should be read in its entirety and
be made permanently available to
the staff responsible for equipment
operation. It should not, however
be considered as a complete code
of practice, nor should it replace
existing codes or standards which
may be applicable. Fulton reserves
the right to change any part of
this installation, operation and
maintenance manual without notice.
Do not install, operate, service,
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional /professional codes or
regulations
Setpoint Configuration
with
Outdoor Reset
The Setpoint Configuration screen displayed is based on the option selected.
Below is the Setpoint Configuration screen without outdoor reset.
FIGURE 24 – SETPOINT CONFIGURATION WITH OUTDOOR RESET
Setpoint Mode:
»
ModSync®:
The ModSync® Setpoint mode will use the outdoor reset
configuration on the next screen.
»
Manual:
When in Manual mode the ModSync® will operate based
on the user selected input.
Outdoor Temp Disable:
If the Outdoor Air Temperature exceeds the
Outdoor Temp Disable value, the ModSync® will disable the boilers and
not allow them to run. The boiler status will change to Outdoor Temp
Disable to show that the boiler has been disabled due to high outdoor air
temperature.
Outdoor Temp Deviation:
Outdoor Temp Deviation is how many degrees
the outdoor air temperature needs to drop before the ModSync® will
re-enable the boilers out of Outdoor Temp Disable. For example, if the
outdoor temp disable is set for 100°F and the outdoor temp deviation is
set for 5°F then the boilers will shut down on outdoor temp disable when
the outdoor temperature reaches 100°F and will not re-enable until the
outdoor temperature drops to 95°F.
Содержание ModSync SE
Страница 2: ...PAGE LEFT INTENTIONALLY BLACK...
Страница 4: ...FultonGroupN A Inc 2021 TABLEOFCONTENTS ModSyncSE User Manual 211020 0 2 PAGE LEFT INTENTIONALLY BLACK...
Страница 14: ...FultonGroupN A Inc 2021 INSTALLATION ModSyncSE User Manual 211020 SECTION2 2 6 PAGE LEFT INTENTIONALLY BLACK...
Страница 54: ...FultonGroupN A Inc 2021 OPERATION ModSyncSE User Manual 211020 SECTION3 3 40 PAGE LEFT INTENTIONALLY BLACK...
Страница 66: ...FultonGroupN A Inc 2021 NETWORK ModSyncSE User Manual 211020 SECTION4 4 12 PAGE LEFT INTENTIONALLY BLACK...
Страница 70: ...FultonGroupN A Inc 2021 MAINTENANCE ModSyncSE User Manual 211020 SECTION5 5 4 PAGE LEFT INTENTIONALLY BLACK...