SECTION 3
ModSyncSE-User-Manual-211020
OPERATION
!
WARNING
This manual is provided as a
guide to the correct operation and
maintenance of your equipment,
and should be read in its entirety and
be made permanently available to
the staff responsible for equipment
operation. It should not, however
be considered as a complete code
of practice, nor should it replace
existing codes or standards which
may be applicable. Fulton reserves
the right to change any part of
this installation, operation and
maintenance manual without notice.
Do not install, operate, service,
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional /professional codes or
regulations
»
General Heat Demand:
Configures the output as a General Heat
Demand. The output will enable whenever any of the boilers receive
a heat demand.
»
System Pump #:
Configures the output for the System Pump. The
output will enable when the corresponding system pump receives a
demand. This selection will only be available if System Pumps have
been enabled.
»
Boiler # Heat Demand:
Configures the output as a boiler heat
demand status. The output will enable whenever the corresponding
boiler has a heat demand.
FIGURE 12 – DIGITAL OUTPUT HARDWARE CONFIGURATION SCREEN
Digital Inputs:
All digital inputs need to be configured for the options
desired before the inputs will operate. Only options that have been
enabled will be selectable along with some preconfigured default options.
All digital inputs are 24VDC and dry contacts should be provided for all
inputs.
»
Boiler # Valve Interlock:
Configures the input for the boiler
isolation valve status interlock. When the boiler receives a heat
demand the ModSync® will enable the isolation valve and then waits
for the isolation valve status interlock input to be received before
sending the enable to the boiler. This selection will only be available
if isolation valves and isolation valve interlocks have been enabled.
»
Boiler # Pump Interlock:
Configures the input for the boiler
circulation pump status interlock. When the boiler receives a heat
demand the ModSync® will enable the boiler pump and then waits
for the pumps status interlock input to be received before sending
the enable to the boiler. This selection will only be available if
boiler circulation pumps and circulation pump interlocks have been
enabled.
Содержание ModSync SE
Страница 2: ...PAGE LEFT INTENTIONALLY BLACK...
Страница 4: ...FultonGroupN A Inc 2021 TABLEOFCONTENTS ModSyncSE User Manual 211020 0 2 PAGE LEFT INTENTIONALLY BLACK...
Страница 14: ...FultonGroupN A Inc 2021 INSTALLATION ModSyncSE User Manual 211020 SECTION2 2 6 PAGE LEFT INTENTIONALLY BLACK...
Страница 54: ...FultonGroupN A Inc 2021 OPERATION ModSyncSE User Manual 211020 SECTION3 3 40 PAGE LEFT INTENTIONALLY BLACK...
Страница 66: ...FultonGroupN A Inc 2021 NETWORK ModSyncSE User Manual 211020 SECTION4 4 12 PAGE LEFT INTENTIONALLY BLACK...
Страница 70: ...FultonGroupN A Inc 2021 MAINTENANCE ModSyncSE User Manual 211020 SECTION5 5 4 PAGE LEFT INTENTIONALLY BLACK...