© Fulton Group N.A., Inc. 2021
3-16
OPERATION
ModSyncSE-User-Manual-211020
SECTION 3
!
WARNING
This manual is provided as a
guide to the correct operation and
maintenance of your equipment,
and should be read in its entirety and
be made permanently available to
the staff responsible for equipment
operation. It should not, however
be considered as a complete code
of practice, nor should it replace
existing codes or standards which
may be applicable. Fulton reserves
the right to change any part of
this installation, operation and
maintenance manual without notice.
Do not install, operate, service,
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional /professional codes or
regulations
»
E-Stop Status:
Configures the input to accept an Emergency
Stop input. This is a status only input and will not shut down the
boilers. The E-Stop must still be wired to each individual boiler.
This configuration is only used to display that the E-Stop has been
pressed on the screen and will also create an alarm condition with
a time and date stamp in the alarm history for when the E-Stop was
pressed.
»
Boiler I/O Configuration Inputs
: The following inputs will only
be available for boilers that have been selected as having an I/O
interface.
y
Boiler # Remote Mode:
Configures the input as the Remote
Mode input from the boiler. This will inform the ModSync®
that the boiler has been selected for remote control and the
ModSync® is allowed to run the boiler.
y
Boiler # Main On:
Configures the input as the Main Valve On
status input from the boiler. This will inform the ModSync®
that the boiler is firing and producing heat. This is necessary for
normal operation as the ModSync® will not assign firing rates
to boilers that are not running.
y
Boiler # Alarm:
Configures the input as the General Alarm
status input from the boiler. This will inform the ModSync®
that the boiler has entered into an alarm state and is no longer
available for lead lag operation.
»
System Pump # Status:
Configures the input as a status input for
the selected pump. This will allow the ModSync® to know that the
associated pump is operating. This selection will only be available if
system pumps have been enabled.
»
System Pump # Alarm:
Configures the input as an alarm input
for the selected pump. If the pump has an available pump output
that can be wired to the ModSync® this can be used to allow the
ModSync® to know that the pump is not available and allow the
ModSync® to select a different pump to use. This selection will only
be available if system pumps have been enabled.
»
Primary Low Water:
Configures the input to annunciate an alarm
when a boilers primary low water is active.
»
Secondary Low Water:
Configures the input to annunciate an alarm
when a boilers Secondary low water is active.
Содержание ModSync SE
Страница 2: ...PAGE LEFT INTENTIONALLY BLACK...
Страница 4: ...FultonGroupN A Inc 2021 TABLEOFCONTENTS ModSyncSE User Manual 211020 0 2 PAGE LEFT INTENTIONALLY BLACK...
Страница 14: ...FultonGroupN A Inc 2021 INSTALLATION ModSyncSE User Manual 211020 SECTION2 2 6 PAGE LEFT INTENTIONALLY BLACK...
Страница 54: ...FultonGroupN A Inc 2021 OPERATION ModSyncSE User Manual 211020 SECTION3 3 40 PAGE LEFT INTENTIONALLY BLACK...
Страница 66: ...FultonGroupN A Inc 2021 NETWORK ModSyncSE User Manual 211020 SECTION4 4 12 PAGE LEFT INTENTIONALLY BLACK...
Страница 70: ...FultonGroupN A Inc 2021 MAINTENANCE ModSyncSE User Manual 211020 SECTION5 5 4 PAGE LEFT INTENTIONALLY BLACK...