SECTION 3
ModSyncSE-User-Manual-211020
OPERATION
!
WARNING
This manual is provided as a
guide to the correct operation and
maintenance of your equipment,
and should be read in its entirety and
be made permanently available to
the staff responsible for equipment
operation. It should not, however
be considered as a complete code
of practice, nor should it replace
existing codes or standards which
may be applicable. Fulton reserves
the right to change any part of
this installation, operation and
maintenance manual without notice.
Do not install, operate, service,
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional /professional codes or
regulations
Lead / Lag Configuration 1
The Lead/Lag Configuration screens are used to configure the rotation schedule
for the Lead Boiler in the loop, PID settings for the Control Variable.
The Lead Lag Screen 1 is used to display the current lead lag status of all the
FIGURE 28 – LEAD / LAG SCREENS PAGE 1
enabled boilers and to determine when the boilers sequence rotates.
Cycles to Auto Rotate:
Determines how many times the lead boiler will
need to cycle, after it has become lead before the sequence is rotated.
Hours to Auto Rotate:
Determines how many hours the lead boiler will
need to run, after it has become lead, before the sequence is rotated.
NOTE:
The Sequence will rotate at whichever condition occurs first.
» When the ModSync® rotates the boilers, the boilers will be
sequenced based on the rotation priority and their overall
statistics. For example: if the rotation is set to Hours, the boiler
with the least number of total hours will be lead, the boiler with
next lowest number of hours will be lag 1 and so on. This may
mean that the lead boiler may not change if the current lead
boiler has the lowest number of hours.
Содержание ModSync SE
Страница 2: ...PAGE LEFT INTENTIONALLY BLACK...
Страница 4: ...FultonGroupN A Inc 2021 TABLEOFCONTENTS ModSyncSE User Manual 211020 0 2 PAGE LEFT INTENTIONALLY BLACK...
Страница 14: ...FultonGroupN A Inc 2021 INSTALLATION ModSyncSE User Manual 211020 SECTION2 2 6 PAGE LEFT INTENTIONALLY BLACK...
Страница 54: ...FultonGroupN A Inc 2021 OPERATION ModSyncSE User Manual 211020 SECTION3 3 40 PAGE LEFT INTENTIONALLY BLACK...
Страница 66: ...FultonGroupN A Inc 2021 NETWORK ModSyncSE User Manual 211020 SECTION4 4 12 PAGE LEFT INTENTIONALLY BLACK...
Страница 70: ...FultonGroupN A Inc 2021 MAINTENANCE ModSyncSE User Manual 211020 SECTION5 5 4 PAGE LEFT INTENTIONALLY BLACK...