© Fulton Group N.A., Inc. 2021
3-12
OPERATION
ModSyncSE-User-Manual-211020
SECTION 3
!
WARNING
This manual is provided as a
guide to the correct operation and
maintenance of your equipment,
and should be read in its entirety and
be made permanently available to
the staff responsible for equipment
operation. It should not, however
be considered as a complete code
of practice, nor should it replace
existing codes or standards which
may be applicable. Fulton reserves
the right to change any part of
this installation, operation and
maintenance manual without notice.
Do not install, operate, service,
or repair any component of this
equipment unless you are qualified
and fully understand all requirements
and procedures.
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional /professional codes or
regulations
System and Scaling Screen 4
Cold Start / Low Fire Hold:
Enable / Disable:
Keeps an idle boiler at or near low fire (user selectable)
for a period of time after it receives a new call for heat.
Off Time:
Amount of time that a boiler must be off or idle for the Cold Start
/ Low fire hold to be active during the next normal call for heat.
Run for:
Amount of time the boiler will remain at or near low fire before
releasing to modulate normally.
Firing Rate:
User selectable low fire or cold start firing rate. User selectable
0-20%
LMV3 Secondary Fuel Configuration:
Operation on LMV3 Secondary Fuel:
For boilers that can operate
determined by the burner setup on oil (or other secondary fuel) the
ModSync® can be configured to operate in two different modes. In
Modulation mode the ModSync® will operate the boiler in full modulation.
In High/Low the ModSync® will operate the boiler as a High/Low/Off
operation.
Min SP On LMV3 Secondary Fuel:
When any boiler is operating in oil the
ModSync® will limit the minimum setpoint to the selected value.
LMV3 Secondary Fuel High Fire S2:
For High/Low/Off boilers only.
Select the calculated firing rate at the ModSync® that determines the point
that the boiler increases to high fire.
LMV3 Secondary Fuel Low Fire S1:
For High/Low/Off boilers only. Select
the calculated firing rate at the ModSync® that determines the point that
the boiler decreases to low fire from high fire.
FIGURE 9 – CONFIGURATION SCREEN
Содержание ModSync SE
Страница 2: ...PAGE LEFT INTENTIONALLY BLACK...
Страница 4: ...FultonGroupN A Inc 2021 TABLEOFCONTENTS ModSyncSE User Manual 211020 0 2 PAGE LEFT INTENTIONALLY BLACK...
Страница 14: ...FultonGroupN A Inc 2021 INSTALLATION ModSyncSE User Manual 211020 SECTION2 2 6 PAGE LEFT INTENTIONALLY BLACK...
Страница 54: ...FultonGroupN A Inc 2021 OPERATION ModSyncSE User Manual 211020 SECTION3 3 40 PAGE LEFT INTENTIONALLY BLACK...
Страница 66: ...FultonGroupN A Inc 2021 NETWORK ModSyncSE User Manual 211020 SECTION4 4 12 PAGE LEFT INTENTIONALLY BLACK...
Страница 70: ...FultonGroupN A Inc 2021 MAINTENANCE ModSyncSE User Manual 211020 SECTION5 5 4 PAGE LEFT INTENTIONALLY BLACK...