4.13.5.5. Range over output and pulse range over output
Description
AO RANGE OVER
: Contact output to DO1, DO2, DO3, and/or DO4 are activated when the flow rate is outside the setting range.
PULSE RANGE OVER : Contact output to DO1, DO2, DO3, and/or DO4 are activated when the total pulse output exceeds the
maximum output frequency value.
AO RANGE OVER(T) : Contact output to DO1, DO2, DO3, and/or DO4 are activated when the thermal energy is outside the setting
range.
(This item is used only in 1-path/energy measurement)
P:RANGE OVER(T) : Contact output to DO1, DO2, DO3, and/or DO4 are activated when the total energy pulse output exceeds the
maximum output frequency value. (This tem is used only in 1-path/energy measurement)
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.5.1.)
Operation
(example)
Set the DO1 output to “AO RANGE OVER”.
Also, set the contact to “ACTIVE ON”.
* Below is an example for 1-path/energy measurement. Refer to Section 4.8.1 for channel designation of 2-path
measurement and 2-pipe measurement.
Key operation
Description
Display
▼
Press the
key twice to display “OUTPUT SETUP”.
OUTPUT SETUP
ENT
▼
Press the
ENT
key once to display “ZERO ADJUSTMENT”.
ZERO ADJUSTMENT
SET ZERO
▼
Press the
key for 8 times to display “DO1 OUT”.
* Use the
key to select “DO2 OUT”, “DO3 OUT”, or “DO4 OUT”.
DO1 OUT
NOT USED
ENT
▼
Press the
ENT
key once to blink the cursor.
DO1 OUT
NOT USED
▼
Press the
key for 7 times to display “AO RANGE OVER” on the 2nd
line.
* Press the
key again to display “PULSE RANGE OVER”.
DO1 OUT
AO RANGE OVER
Press the
ENT
key once to register “RANGE OVER”.
DO1 OUT
COMPLETE
↓
ENT
▼
▼
▼
▼
―――
“RANGE OVER” has been registered.
―――
STATUS OUT
CONTACT ACTION
ENT
▼
Press the
ENT
key once to display “CONTACT ACTION”.
CONTACT ACTION
ACTIVE ON
Press the ENT
key once to register “ACTIVE ON”(normally off).
* To select normally
on
, press the
key.
CONTACT ACTION
COMPLETE
↓
ENT
▼
▼
▼
▼
―――
“ACTIVE ON” has been registered.
―――
STATUS OUT
CONTACT ACTION
ESC
Press the
ESC
key twice and then press the
key for 3 times to enter
the measurement mode.
0.000 %
0.000 m3