-85-
4.14.1.3. Calibrating the temperature
Description
CALIBRATION ZERO and CALIBRATION SPAN: Used to calibrate measured value manually.
Zero point and/or span can be calibrated. Calibration equation is shown below.
Temperature =
Measured value
×
[Set span value %]
100
+ Zero point
DAMPING : Used to reduce fluctuation of measured value.
The default value is a time constant. (Response time: approx. 63%)
SETTING : Used when calculating thermal energy based on set temperature, instead of temperature input.
Settable
range
1. Supply temperature : TS INPUT
CALIBRATION ZERO (-40 to 40°C (factory set: 0°C))
CALIBRATION SPAN (50 to 150% (factory set: 100%))
DAMPING (0 to 120sec(factory set: 5sec))
SETTING
TEMPERATURE (-40 to 200°C (factory set: 25°C))
2. Return temperature : TR INPUT
CALIBRATION ZERO (-40 to 40°C (factory set: 0°C))
CALIBRATION SPAN (50 to 150% (factory set: 100%))
DAMPING (0 to 120sec(factory set: 5sec))
SETTING
TEMPERATURE (-40 to 200°C (factory set: 25°C))
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.5.1.)
Operation
(example)
Change the value of DAMPING of SUPPLY TEMP. and RETURN TEMP. to “10sec”.
Key operation
Description
Display
▼
Press the
key for 3 times to display “OUTPUT SETUP”.
OUTPUT SETUP
ENT
▼
Press the
ENT
key once to display “MEASUREMENT MODE”.
MEASUREMENT MODE
1 PATH
▼
Press the
key for 8 times to display “ENERGY MODE”.
ENERGY MODE
ENT
▼
Press the
ENT
key once to display “MODE”.
MODE
USED
▼
Press the
key once to display “SUPPLY TEMP.”.
SUPPLY TEMP.
TS INPUT
ENT
▼
Press the
ENT
key once to blink the cursor.
SUPPLY TEMP.
TS INPUT
ENT
▼
Press the
ENT
key once to display “CALIBRATION ZERO”.
CALIBRATION ZERO
0.0 ℃
▼
Press the
key twice to display “DAMPING”.
DAMPING
5 sec
ENT
▼
Press the
ENT
key once to blink the cursor.
DAMPING
005 sec
▼
▼
▼
▼
Use the
key to move the cursor, and the
key to change the
value.
0
0
5 sec
0
1
5 sec
01
0
sec
Press the
ENT
key once to register.
DAMPING
COMPLETE
↓
ENT
▼
▼
▼
▼
―――
“DAMPING” has been registered.
―――
DAMPING
10 sec
ESC
▼
Press the
ESC
key once to display “SUPPLY TEMP.”
SUPPLY TEMP.
TS INPUT
▼
Press the
key once to display “RETURN TEMP.”
RETURN TEMP.
TR INPUT
Temperature conversion table
°C K F
-40 233.15 -40.00
0
273.15
32.00
40
313.15
104.00